2-27. E: 86. High pressure switch error (Outdoor unit)
Indicator
Wired remote
controller
Error code E: 86
Detective actuator
Outdoor unit main PCB
When pressure switch open is detected in 10 seconds
after the power is turned on.
High pressure switch
Forecast of cause
High pressure switch connector disconnection or open
High pressure switch characteristics failure
Main PCB failure
Check point 1. Check the high pressure switch connection state
Check connector and wiring connection state.
Check if cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Check the high pressure switch characteristics
Check switch characteristics.
For the characteristics of the high pressure switch, refer to below.
Check point 3. Replace main PCB
Change main PCB and check operation again.
End
Type of contact
C
H
Pressure
Characteristics of pressure switch
Pressure switch 1
Contact: Short → Open 4.2±0.1 MPa
Contact: Open → Short 3.2 ± 0.15 MPa
36/45/54 model: P770
2-27. E: 86. High pressure switch error (Outdoor unit)
- (03-34) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu RCG24KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu RCG24KVLA and is the answer not in the manual?

Fujitsu RCG24KVLA Specifications

General IconGeneral
BrandFujitsu
ModelRCG24KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals