1. Compressor frequency control
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
frequency of the compressor.
If the room temperature is 6.0 °C higher than a set temperature, the compressor operation fre-
quency will attain to maximum performance.
If the room temperature is 1.0 °C lower than a set temperature, the compressor will be stopped.
When the room temperature is within the range of +6.0°C to -1.0°C of the setting temperature, the
compressor frequency is controlled within the range shown in the table below. However, the maxi-
mum frequency is limited in the range shown in the figure below based on the indoor fan mode
and the outdoor temperature.
¢ Compact cassette type
Compressor frequency range
Connected model name Minimum frequency Maximum frequency
AOHG36KBTB 15 rps 98 rps
AOHG45KBTB 17 rps 95 rps
AOHG54KBTB 17 rps 95 rps
1-1. Cooling operation - (01-1) - 1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Other manuals for Fujitsu RCG24KVLA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu RCG24KVLA and is the answer not in the manual?

Fujitsu RCG24KVLA Specifications

General IconGeneral
BrandFujitsu
ModelRCG24KVLA
CategoryAir Conditioner
LanguageEnglish

Related product manuals