1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation fre-
quency of compressor.
If the room temperature is 6.0 °C lower than a set temperature, the compressor operation frequen-
cy will attain to maximum performance.
If the room temperature is 1.0 °C higher than a set temperature, the compressor will be stopped.
When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
compressor frequency is controlled within the range shown below.
Compressor frequency range
Connected model name Minimum frequency Maximum frequency
AOHG36KBTB 15 rps 120 rps
AOHG45KBTB 17 rps 120 rps
AOHG54KBTB 17 rps 120 rps
1-2. Heating operation - (01-5) - 1. Compressor frequency control