EasyManua.ls Logo

Fujitsu RSG12LMCA

Fujitsu RSG12LMCA
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. HEATING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 3°C than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is some degrees higher than a set temperature,
the compressor will be stopped.
* When the room temperature is between +2.5°C to -3°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table 3.
However, the maximum frequency is limited shown in Table 4 based on the fan mode.
( Table 3 : Compressor frequency range )
01-02
Minimum
frequency
Maximum
frequency
07/09 22rps 99rps
12
18rps 120rps
14
18rps 119rps
Model

Related product manuals