05-22
1. Discharge Pressure Sensor - Pressure Sensor (HIGH): CN118 -
4.5
5.00
0.5
0
Output [V]
Pressure [MPa]
With the connector connected to the PCB, measure the voltage
between CN119 : 2-3 of the Main PCB.
2. Suction Pressure Sensor - Pressure Sensor (Low): CN119 -
3.5
1.70
0.5
0
Output [V]
Pressure [MPa]
DC
5-3-1 Pressure senser
5-3 CHARACTERISTICS OF SENSORS
Pressure
(MPa)
Output
(V)
0.00 0.10 0.20 0.30 0.40 0.50 0.70 0.80 0.90 1.00 1.20 1.40 1.60 1.80 2.00
Pressure
(MPa)
Output
(V)
0.50 0.58 0.66 0.74 0.82 0.90 1.06 1.14 1.22 1.30 1.46 1.62 1.78 1.94 2.10
2.20 2.40 2.60 2.80 3.00 3.20 3.40 3.60 3.80 4.00 4.20 4.40 4.60 4.80 5.00
2.26 2.42 2.58 2.74
2.90 3.06 3.22 3.38 3.54 3.70 3.86 4.02 4.18 4.34 4.50
Pressure
(MPa)
Output
(V)
0.00 0.10 0.20 0.30 0.40 0.50 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70
0.50 0.68 0.85 1.03 1.21 1.38 1.74 1.91 2.09
2.27 2.44 2.62 2.79 2.97 3.15 3.32 3.50
With the connector connected to the PCB, measure the voltage
between CN118 : 2-3 of the Main PCB.
DC

Table of Contents

Other manuals for Fujitsu UTY-VDGX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu UTY-VDGX and is the answer not in the manual?

Fujitsu UTY-VDGX Specifications

General IconGeneral
BrandFujitsu
ModelUTY-VDGX
CategoryAir Conditioner
LanguageEnglish

Related product manuals