EasyManuals Logo

Fujitsu UTY-VDGX User Manual

Fujitsu UTY-VDGX
255 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #87 background imageLoading...
Page #87 background image
Trouble shooting 9 E26. 4
INDOOR UNIT Error Method:
Address Duplication in Wired remote
contorller system
Indicate or Display:
Indoor Unit : Operation LED 2 times Flash, Timer LED 6 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 2 6
Detective Actuators:
Wired remote controller ( 2-Wire )
Indoor unit Controller PCB circuit
Detective details:
When the duplicated address number exists in one RCgroup
Check Point 3 : Check Indoor unit controller PCB
Forecast of Cause : 1. Wrong wiring of RCgroup 2. Wrong remote address setting 3. Indoor unit controller PCB failure
4. Remote controller failure
Check Point 1 : Wire installation
Wrong wire connection in RCgroup (Please refer to the installation manual)
Change controller PCB and check the Error after setting remote controller address
Check if controller PCB damage
Check Point 2 : Wrong RCgroup setting
The duplicated address number is not existing in one RCgroup
04-17

Table of Contents

Other manuals for Fujitsu UTY-VDGX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu UTY-VDGX and is the answer not in the manual?

Fujitsu UTY-VDGX Specifications

General IconGeneral
BrandFujitsu
ModelUTY-VDGX
CategoryAir Conditioner
LanguageEnglish

Related product manuals