Trouble shooting 16 E32. 7
INDOOR UNIT Error Method:
Indoor unit microcomputer
self-check error
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
When the error is detected by the self-diagnosis of a microcomputer
Forecast of Cause :
1. Outside cause 2. Defective connection of electric component 3. Controller PCB defective
Check Point 1-2 :
Check outside cause (Voltage drop or noise, etc.)
Instant drop --- Check if there is a large load electric apparatus
in the same circuit.
Momentary power failure ----- Check if there is a defective
contact or leak current in the
power supply circuit.
Noise ----- Check if there is any equipment causing harmonic
wave near electric line (Neon bulb or electric
equipment that may cause harmonic wave).
Check the complete insulation of grounding.
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Check Point 1-1 : Reset Power Supply
Check Point 2 :
Check Indoor Unit electric components
YES
NO
Does abnormal LED indication show again?
Check all connectors (loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
OK
04-24

Table of Contents

Other manuals for Fujitsu UTY-VDGX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu UTY-VDGX and is the answer not in the manual?

Fujitsu UTY-VDGX Specifications

General IconGeneral
BrandFujitsu
ModelUTY-VDGX
CategoryAir Conditioner
LanguageEnglish

Related product manuals