- (CS01 - 56) -
Control system
- (CS01 - 56) -
CONTROL
SYSTEM
CONTROL
SYSTEM
Input / output test functions
z
Input/output testing is used to ensure that the
connected components are in working order.
Relay Output Testing
Selection of a setting from relay testing closes the
corresponding relay and therefore switches on the
connected component. This makes it possible to
check that the relays are in working order and that
the wiring has been performed correctly.
LINE FUNCTION
7700 Relay test
This consists of instructing the regulator's relays one by one and checking their outputs. This enables you to
check that the relays are working and that the cabling is correct. Check that each appliance in the installation
is operating correctly.
(0) No test
(1) Everything is on STOP
(2) Relay output QX1 : heat pump CC1 (Main
regulation board)
(3) Relay output QX2 : Electrical back-up (1st stage)
or Boiler connection distribution valve
(4) Relay output QX3 : Electrical back-up (2nd stage)
or Boiler connection contact
(5) Relay output QX4 : DHW distribution valve
(6) Relay output QX5 : DHW Electrical back-up
(7) Relay output QX6
(8) Relay output QX31 : Heat circ mix valve open Y1
(9) Relay output QX32 : Heat circ mix valve close Y2
(10) Relay output QX33 : heat pump CC2
(11) Relay output QX34
(12) Relay output QX35 : Swimming pool distribution
valve
(13) Relay output QX21 module 1
(14) Relay output QX22 module 1
(15) Relay output QX23 module 1
(16) Relay output QX21 module 2
(17) Relay output QX22 module 2
(18) Relay output QX23 module 2
(19) Not used
(20) Not used
(21) Not used
The display shows the “Key” symbol. Pressing the Info button displays "Error 368".
Warning: The component being tested is receiving electr
Warning:
During testing of an output, the heat pump is
s
topped, all outputs are "off" and only the controlled
output is on.
Analog Input/Output Testing
LINE FUNCTION
7710 Output test UX1
7712 PWM signal UX1
7722 Cooling mode DO2
7723 Heat pump D3
7724 Output test UX3
7725 Voltage value UX3
Cooling mode DO2
Shows the output status.
Output test UX3
Enables testing the outdoor unit control.
Sensor Input Testing
LINE FUNCTION
7820 Sensor temp BX1
7821 Sensor temp BX2
7822 Sensor temp BX3
7823 Sensor temp BX4
Displays the temperature of each sensor.