WARRANTY & PARTS ModSyncSE-User-Manual-211020 SECTION 6
6-2
Questions? Call (315) 298-8510, or visit us online at www.fulton.com
67
Factory Default Settings
Lead/Lag Configuration
System Configuration
Shoulder
Design
Lead/Lag configuration
Cycles to Auto Rotate
20
Lead Rotation Priority
Hours to Auto Rotate
10
Manual Rotation Priority
Hours
Max # of Boilers to Run
User Defined at Startup
Setpoint Scaling
Low
High
Lag Boiler Start Delay
1:00
1:00
80
180
Lag Boiler Stop Delay
1:00
1:00
System Configuration
Lag Boiler Start
5
5
Boilers
Lag Boiler Stop
5
5
Transition Delay
Modulation at Next Stage CV
20
20
Screen Contrast
1
st
Lag Stage Start CV
20
20
Temp Scaling
1
st
Lag Stage Stop CV
10
10
Modulation Mode
Additional Lag Enabled CV
10
10
Outlet Monitoring
Proportional Band
60
60
Enable/Disable
Integral Time
20
20
Temp > SP By
Derivative Time
0
0
Low Fire %
Setpoint Configuration
Temp Deviation
Setpoint Mode
Modsync
Outlet Scaling
Low
High
Manual Setpoint
120
0
210
DHW Priority
Disabled
-If- Oil Configuration is Required
DHW Min Setpoint
120
Operation in Oil
Minimum Setpoint
80
Min SP on Oil
Maximum Setpoint
180
Oil High Fire S2
-If- Outdoor Sensor is Enabled
Oil Low Fire S1
Outdoor Temp Disable
100
Boiler Alarm Config
Outdoor Temp Deviation
5
Boiler Alarm Delay
Occupied Mode Reset Curve
Loop
OA
Sensor Alarm Delay
120.0
50.0
Enable after Alarm
160.0
0.0
Boiler Monitor Alarm
Unoccupied Reset Curve
Boiler Monitor Delay
110.0
50.0
Boiler Monitor Retry
150.0
0.0
Monitor Retry Delay
Setback Schedule Configuration
-If- System Pumps are Enabled
Occupied
Unoccupied
Pump Monitor Alarm
Monday
6:00
20:00
Pump Monitor Delay
Tuesday
6:00
20:00
Pump Monitor Retry
Wednesday
6:00
20:00
Monitor Retry Delay
Thursday
6:00
20:00
-If- Proving Interlock is Enabled
Friday
6:00
20:00
Proving Interlock Alarm
Saturday
8:00
18:00
Interlock Alarm Delay
Sunday
8:00
18:00
Factory Default Settings