1 Introduction
This new generation of low-cost, microprocessor-based control incorporates two bright, easy to read LCD
displays which indicate process value (PV) and set point (SP). The control is powered by an 11-26 VDC
supply and incorporates a 2 Amp control relay output as a standard. The control is fully programmable for
PT100 RTD and thermocouple types J, K, T, E, B, R, S, N, L, U, P, C, and D. The input provides high
accuracy via an 18-bit A to D converter and when coupled with the fast-sampling rate, allows control of fast
processes.
1.1 Features
LCD display
Simple operation
Universal input (thermocouple/RTD) with high accuracy 18-bit A-D conversion
Fast sampling rate
Degrees F or C operation
Low voltage operation
Programmable deadband alarm
Power failure alarm
Low battery indication
Adjustable hysteresis for control and alarm outputs
Process value calibration offset adjustment
Control and alarm relay (SPST) output contacts
Audible alarm with silence (utilizing external relay)
The FDC-C42 microprocessor-based controller, incorporates dual, easy to read 4-digit LCD readouts to
indicate process value and set point, as well as other controller operations. The unit features keys to select
the various operator views as well as control parameters. The FDC-C42 chamber controller is provided
pre-configured, specifically for low temperature chamber operation, providing simple to use, “hassle” free
operation for startup and operation of the chamber.
The FDC-C42 incorporates a (SPST) control relay output and three (SPST) alarm relay outputs. Two of
the alarm relays (AL1 for temperature and AL2 for power failure) are prewired together in order to facilitate
faster installation and connection to external alarm relays for remote indication and sounding the on-board
audible alarm (wired separately). A programmable deadband alarm set point allows the operator to
monitor/indicate alarm conditions above and below chamber operational settings.
The FDC-C42 provides digital inputs which are utilized for the power failure and low battery indicators
(compatible with MEAN WELL DRC-40/60 series power supplies). When main power is lost, the external
12Vdc backup battery will maintain power to the FDC-C42; however, the “power OK” input will be
deactivated causing the second alarm relay output (AL2) to activate and sound the audible alarm. A silence
push-button is provided for the audible alarm, so that when a temperature and/or power failure alarm
occurs, the operator can silence the alarm.

Other manuals for Future Design FDC-C42

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Future Design FDC-C42 and is the answer not in the manual?

Future Design FDC-C42 Specifications

General IconGeneral
BrandFuture Design
ModelFDC-C42
CategoryController
LanguageEnglish