IOM GMI 2M & 2ML Nov 2010.doc
10
WARNING
Exceeding the maximum allowable gas manifold pressure could result in
over-firing of the unit and may cause permanent damage to the unit.
NOTES
¾ Air and gas flow rates are factory adjusted for optimum combustion
quality. Note that these settings may vary slightly at different site
conditions (calorific value of gas, duct length, etc.).
¾ After installation is completed, using a gas analyzer, the CO and O
2
contents of the exhaust gases should be re-checked to ensure their
compliance with those achieved at the factory and reflected in the test
report provided to your local Gasmaster representative.
¾ IF adjustments to the factory settings of air and gas flows are made,
ensure that the manifold gas pressure does not exceed the pressure
specified on the boiler label.