EasyManua.ls Logo

GE Security FireShield FS302 - Page 44

GE Security FireShield FS302
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Calculations
A.2 FireShield Technical Reference Manual
Form A
Module Quantity
Standby
current
(mA)
Qty × Standby
current (mA)
Alarm
current
(mA)
Qty × Alarm
current (mA)
FSRSI [1] 12 48
FSRZI-A [1] 8 35
FSRRM common [1] 30 41
FSRRM zone [1] 8 65
Other AUX
Total AUX [5] [6]
Form B
(Note: Calculate IDC detector load or use maximum load.)
IDC
Quantity of
detectors [2]
Detector current
(mA) [3]
Total standby current [4]
(quantity x current in mA)
IDC1
IDC2
IDC3
IDC4
IDC5
IDC6
IDC7
IDC8
IDC9
IDC10
Total current for all IDCs =
Max IDC standby current: FS302 = 4.5 mA, FS502 = 7.5 mA, and FS1004 = 15.0 mA
Notes
[1] Use of FSRSI, FSRZI-A, and FSRRM is limited as follows: Three- and five-zone panels support 2 FSRSIs, 2 FSRZI-As, and 4
FSRRMs, ten-zone panels support 2 FSRSIs, 4 FSRZI-As, and 6 FSRRMs.
[2] See the FireShield UL and ULC Compatibility List (P/N 3100468) for the maximum number of detectors per IDC.
[3] See FireShield UL and ULC Compatibility List (P/N 3100468) for detector current ratings.
[4] Maximum current per IDC may not exceed 1.5 mA.
[5] Aux power supplied by panel cannot exceed 0.5 A. If more than 0.5 A is required, you must use a compatible UL/ULC listed
fire alarm power supply.
[6] When using an auxiliary power supply, you must connect the -24 OUT connection on the panel to the negative connection on
the auxiliary power supply. Refer to the installation section for more information.

Table of Contents

Related product manuals