3 SETUP AND USE
g
GE Power Management
60
/(9(
/
,1)250$7,21 /,1( (;3/$1$7,21 ',$*126,6 5()
11
STARTS/HOUR TRIP
LOCKOUT TIME = XXX MIN.
Total number of motor starts over
the past hour greater than
Number of Starts / Hour setpoint.
Reduce number of starts during
normal motor operation.

12
ACCEL. TIME TRIP
Motor did not enter a normal
running state (i.e. phase current <
FLC) within Acceleration Time
setpoint.
Excessive load or locked rotor on
start.

13
PHASE REVERSAL TRIP
Phases not connected to motor
in proper sequence.
Check incoming phase
sequence and CT polarity.

14
SPEED SWITCH TRIP
Non-closure of speed switch
contacts within Speed Switch
Time Delay.
Locked rotor on start.

15
DIFFERENTIAL INPUT TRIP
Closure of differential relay
contacts.
Differential relay trip.

16
SPARE INPUT TRIP
Spare Input contact closure. Check device connected to
Spare Input terminals.

17
OVERLOAD WARNING
TIME TO TRIP = XXXXX
Phase current greater than
Immediate O/L Level setpoint.
Reduce motor load.

18
G/F ALARMS
G/F = XX.X AMPS
Ground Fault Alarm Level
exceeded for a time greater than
the Ground Fault Time Delay.
Check motor windings for shorts,
moisture, or conductive particles.

19
U/B ALARM
U/B = XX PERCENT
Unbalance Alarm Level
exceeded for a time greater than
the Unbalance Time Delay.
Check incoming phases for
unbalance.

20
U/C ALARM
I(3 ph avg) = XXXX A RMS
Phase current less than
Undercurrent Alarm Level for a
time greater than the
Undercurrent Time Delay.
Check system for loss of load.

21
STATOR RTD ALARM
RTD # X = XXX C
Stator RTD Alarm Level
temperature exceeded on at
least one stator RTD.
Check motor ventilation and
ambient temperature.

22
RTD ALARM
RTD # XX = XXX C
RTD Alarm Level temperature
exceeded.

23
BROKEN RTD LINE
see RTD ACTUAL VALUES
Open circuit on RTD. Check continuity of RTDs.


24
SPARE INPUT ALARM
Spare Input contact closure. Check device connected to
Spare Input terminals.

25
SLAVE NUMBER XXX
NOT CONNECTED
Indicated relay SLAVE number is
not connected or not responding.
Check indicated relay SLAVE.
Check communication link wiring
