3 SETUP AND USE
g
GE Power Management
75
Table 3-7 Preset Factory Relay Configurations and Functions
OUTPUT RELAY
CONFIGURATION/FUNCTION
TRIP ALARM AUX. 1 AUX. 2
CONFIGURATION
Latched (Manual Reset) X X
+
Unlatched (Automatic Reset) X X
+
Fail-safe X X
+
Non-fail-safe X X
+
ALARM SIGNALS
Immediate O/L Warning #
G/F Alarm X
U/B Alarm X
U/C Alarm #
Stator RTD Alarm X
*
X
+
RTD Alarm X
*
X
+
Broken Sensor Alarm #
*
#
+
Self Test Alarm X
*
X
+
Spare Input Alarm
TRIP SIGNALS
O/L Trip X
U/B Trip X
Single Phase Trip X
S/C Trip #
Rapid Trip X
Stator RTD Trip X
RTD Trip X
G/F Trip X
Phase Reversal Trip #
Acceleration Time Trip X
Starts/Hour Trip X
Speed Switch Trip #
Differential Relay Trip #
Spare Input Trip #
Start Inhibit #
*
Model 169 only X Function programmed ON
+
Model 169 Plus only # Function programmed OFF