Table 3-6 Pre-stored Factory Setpoints (169 Setpoint pages 1 to 3)
INFORMATION LINE
FACTORY
VALUE
INFORMATION LINE
FACTORY
VALUE
INFORMATION LINE
FACTORY
VALUE
PAGE 1: SETPOINT VALUES
MOTOR AMPS SETPOINTS
PHASE CT RATIO
SECONDARY = X AMP
PHASE CT RATIO
CT RATIO = XXX:5
MOTOR FULL LOAD CURRENT
FLC = XXXX AMPS
ACCEL.TIME= XX.X SECONDS
Consult motor data sheet
STARTS/HOUR= X
Consult motor data sheet
UNBALANCE ALARM LEVEL
U/B ALARM= XX PERCENT
U/B ALARM TIME DELAY
TIME DELAY = XXX SEC
UNBALANCE TRIP LEVEL
U/B TRIP= XX PERCENT
U/B TRIP TIME DELAY
U/B DELAY= XXX SECONDS
G/F CT RATIO :5 ? XXX
(No indicates 2000:1)
G/F CT RATIO
G/F C.T XXX :5
GROUND FAULT ALARM LEVEL
G/F ALARM= XXX AMPS
G/F ALARM TIME DELAY
TIME DELAY = XXX SEC
GROUND FAULT TRIP LEVEL
G/F TRIP = XXX AMPS
G/F TRIP TIME DELAY
G/F DELAY= XX.X SECONDS
UNDERCURRENT ALARM LEVEL
U/C ALARM= XXX AMPS
UNDERCURRENT TIME DELAY
U/C DELAY= XXX SECONDS
RAPID TRIP / MECH. JAM
TRIP LEVEL= X.X X FLC
RAPID TRIP TIME DELAY
DELAY= X.X X FLC
SHORT CIRCUIT TRIP LEVEL
S/C TRIP= XX X FLC
5
100
90 A
10 s
3
10%
5 s
IMMEDIATE OVERLOAD
LEVEL = X.XX X FLC
PAGE 2: SETPOINT VALUES
RTD SETPOINTS
# OF STATOR RTDS USED
# OF RTDs = X
STATOR #1 ALARM LEVEL
= XXX DEGREES C
STATOR #1 TRIP LEVEL
= XXX DEGREES C
STATOR #2 ALARM LEVEL
= XXX DEGREES C
STATOR #2 TRIP LEVEL
= XXX DEGREES C
STATOR #3 ALARM LEVEL
= XXX DEGREES C
STATOR #3 TRIP LEVEL
= XXX DEGREES C
STATOR #4 ALARM LEVEL
= XXX DEGREES C
STATOR #4 TRIP LEVEL
= XXX DEGREES C
STATOR #5 ALARM LEVEL
= XXX DEGREES C
STATOR #5 TRIP LEVEL
= XXX DEGREES C
STATOR #6 ALARM LEVEL
= XXX DEGREES C
STATOR #6 TRIP LEVEL
= XXX DEGREES C
RTD #7 ALARM LEVEL
= XXX DEGREES C
RTD #7 TRIP LEVEL
= XXX DEGREES C
RTD #8 ALARM LEVEL
= XXX DEGREES C
RTD #8 TRIP LEVEL
= XXX DEGREES C
RTD #9 ALARM LEVEL
= XXX DEGREES C
RTD #9 TRIP LEVEL
= XXX DEGREES C
RTD #10 TRIP LEVEL
= XXX DEGREES C
PAGE 3: SETPOINT VALUES
O/L CURVE SETPOINTS
CUSTOM CURVE? XXX
YES voids selected curve
SELECTED CURVE NUMBER
CURVE # = XX