5–4 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
QUICK SETUP SETTINGS CHAPTER 5: QUICK SETUP - FRONT CONTROL PANEL
PH IOC1 FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
↘
PH IOC1 PICKUP
Range: 0.05 to 20.00 x CT
Default: 1.00 x CT
GND IOC1 FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
↘
GND IOC1 PICKUP
Range: 0.05 to 20.00 x CT
Default: 1.00 x CT
SENS GND IOC1 FUNCTION [WHEN SPECIFICALLY ORDERED]
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
↘
SENS GND IOC1 PICKUP
Range: 0.005 to 3.000 x CT
Default: 1.000 x CT
NTRL IOC1 FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
↘
NTRL IOC1 PICKUP
Range: 0.05 to 20.00 x CT
Default: 1.00 x CT
NOTE:
The settings changed using the Quick Setup menu, are available for review and
modification by navigating through S1 RELAY SETUP, S2 SYSTEM SETUP and S3
PROTECTION in the SETPOINTS main menu.