6–42 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S3 PROTECTION CHAPTER 6: SETPOINTS
Figure 6-17: Phase time overcurrent protection logic diagram
SETPOINTS
Phase A current (IA)
SETPOINT
PH TOC FUNCTION:
Disabled = 0
Latched Alarm
PH TOC PICKUP:
PH TOC CURVE:
PH TOC TDM:
AND
Phase B current (IB)
Phase C current (IC)
OR
Operate Output Relay 1 (TRIP)
Event Recorder
Transient Recorder
LED: PICKUP
LED: TRIP
OR
Event Recorder
Transient Recorder
Alarm
OR
OR
Cold Load PKP
Phase Currents
Adjust Phase TOC PKP
AND
SETPOINTS:
Do Not Operate, Operate
OUTPUT RELAY X
Trip
AND
Trip
(To Breaker Failure)
PH TOC PH A OP
PH TOC PH B OP
PH TOC PH C OP
Message
:
PH TOC OP
PH TOC PH A PKP
PH TOC PH B PKP
PH TOC PH C PKP
PH TOC PKP
PH TOC RESET TIME:
RUN IA > PICKUP
RUN IB > PICKUP
RUN IC > PICKUP
Adjust PKP
Adjust PKP
Adjust PKP
SETPOINTS
BLOCK 1:
Off = 0
BLOCK 2:
Off = 0
BLOCK 3:
Off = 0
OR
Autoreclose
(per shot settings)
LED: ALARM
RESET
Command
AND
S
R
LATCH
898010A2.cdr
Block TOC Dir Phase A
From TOC PHASE DIRECTIONAL
Block TOC Dir Phase B
Block TOC Dir Phase C
AND
AND AND