CHAPTER 6: SETPOINTS S3 PROTECTION
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6–77
Figure 6-33: Phase Overvoltage logic diagram
Phase Voltage Inputs
(associated setpoints)
SETPOINTS
Vab
SETPOINT
PH OV FUNCTION:
Disabled = 0
Latched Alarm
PH OV PICKUP:
AND
Vbc
Vca
Operate Output Relay 1 (TRIP)
Event Recorder
Transient Recorder
LED: TRIP
Alarm
OR
OR
AND
SETPOINTS:
Do Not Operate, Operate
OUTPUT RELAY X
Trip
AND
Trip
(To Breaker Failure)
SETPOINTS
BLOCK 1:
Off = 0
BLOCK 2:
Off = 0
BLOCK 3:
Off = 0
OR
RUN
RUN
RUN
Van
Vbn
Vcn
None
DeltaWye
LED: PICKUP
Event Recorder
Transient Recorder
Phase Overvoltage
Message
Va > PICKUP
Vb > PICKUP
Vc > PICKUP
All Three
Operate for
programmed
combination
Any Two
Any One
SETPOINT
PH OV PHASES:
OR
PHASE OV DELAY:
SETPOINT
t
PKP
LED: ALARM
RESET
Command
AND
S
R
LATCH
898013A1.cdr