6–88 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S3 PROTECTION CHAPTER 6: SETPOINTS
Figure 6-39: Underfrequency logic diagram
Phase Voltage Inputs
(associated setpoints)
SETPOINTS
Vab
SETPOINT
UNDERFREQ FUNCTN:
Disabled = 0
Latched Alarm
UNDERFREQ PKP:
Vbc
Vca
Operate Output Relay 1 (TRIP)
Event Recorder
Transient Recorder
LED: TRIP
Alarm
OR
OR
AND
SETPOINTS
Do Not Operate, Operate
OUTPUT RELAY X
Trip
AND
Trip
(To Breaker Failure)
SETPOINTS
BLOCK 1:
Off = 0
BLOCK 2:
Off = 0
BLOCK 3:
Off = 0
OR
RUN
Van
Vbn
Vcn
None
AND
DeltaWye
LED: PICKUP
Event Recorder
Transient Recorder
Underfrequency1(2)
Message
f < PICKUP
Frequency
Measurement
f ( Va) - frequency
Va > Minimum
MIN VOLTAGE:
SETPOINT
f = 0
UNDERFREQ DELAY:
SETPOINT
t
PKP
LED: ALARM
RESET
Command
AND
S
R
LATCH
898004A1.cdr