6–104 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S3 PROTECTION CHAPTER 6: SETPOINTS
PICKUP DELAY
Range: 0.000 to 60.000 s in steps of 0.001 s
Default: 20.000 s
This setting specifies the pickup time delay for this function to operate after broken
conductor pickup. The time delay should be programmed to a sufficient length to ensure
coordination with external fault clearing and with the dead time of any single-phase
reclosers.
OUTPUT RELAY X
For details see Common setpoints
.
BLOCK 1/2/3
For details see Common setpoints
.