6–108 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S3 PROTECTION CHAPTER 6: SETPOINTS
Figure 6-48: Positive sequence undervoltage logic diagram
Positive Sequence
Voltage
(computed)
SETPOINTS
SETPOINT
POS SEQ UV FUNCTION:
Disabled = 0
Latched Alarm
POS SEQ UV PKP:
POS SEQ UV CURVE:
POS SEQ UV DELAY:
AND
Operate Output Relay 1 (TRIP)
Event Recorder
Transient Recorder
LED: ALARM
LED: TRIP
Alarm
OR
OR
AND
AND
RESET
Command
SETPOINTS
Do Not Operate, Operate
OUTPUT RELAY X
Trip
AND
Trip
(To Breaker Failure)
OR
SETPOINTS
BLOCK 1
Off = 0
BLOCK 2:
Off = 0
BLOCK 3:
Off = 0
OR
RUN
V_1
PICKUP
V_1 > Minimum
POS SEQ UV MIN V:
SETPOINT
AND
LED: PICKUP
Event Recorder
Transient Recorder
Pos Seq Undervoltage
Message
898853A1.cdr