EasyManua.ls Logo

GE 350-A9

GE 350-A9
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6–110 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S3 PROTECTION CHAPTER 6: SETPOINTS
VOLTAGE MODE
Range: Phase-ground, Phase-phase
Default: Phase-ground
If the Phase VT Connection is set to "Wye", then the Voltage Mode setting further defines
the operating quantity and per-unit value for this element.
When "Phase-ground" is selected, the relay applies the phase-to-ground nominal
voltage programmed as VT Secondary from Voltage Sensing menu.
When "Phase-phase" voltage mode is selected, then the computed phase-phase voltage
as an operating quantity is referenced with respect to the phase-to-phase nominal
voltage, that the relay calculates when multiplying the programmed phase-ground
nominal voltage and the square root of 3.
If the Phase VT Connection (set under
SETPOINTS > S2 SYSTEM SETUP > VOLTAGE SENSING
> VT CONNECTION
is set to "Delta", then the programmed phase-to-phase nominal
voltage is used to define the per-unit value, regardless of the Voltage Mode selection.
PICKUP
Range: 0.80 to 4.00 V/Hz in steps of 0.01 V/Hz
Default: 1.05 x V/Hz
Enter the pickup value (multiple of V/Hz), above which the volts-per-hertz element will
pickup. For example, if Phase VT Secondary and Nominal Frequency are set to 120 V and
60 Hz respectively, and Pickup is set to 1.05 x (V/Hz) then the volts-per-hertz element will
pickup, when the actual division of the measured volts by the detected frequency is above
2.1.
CURVE
Range: Definite Time, Inverse A, Inverse B, Inverse C, FlexCurve A, FlexCurve B
Default: Definite TIme
Definite Time:
For the definite time curve, T(s) = TD multiplier. For example, setting the TD multiplier to
20 results a time delay of 20 seconds to operate when above the Volts/Hz pickup setting.
Inverse Curve A:
The curve for the Volts/Hertz Inverse Curve A shape is derived from the formula:
where:
T = Operating Time
TDM = Time Delay Multiplier (delay in seconds)
V = fundamental RMS value of voltage
F = frequency of voltage signal
Pickup = volts-per-hertz pickup setpoint

Table of Contents

Other manuals for GE 350-A9

Related product manuals