6–142 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S4 CONTROLS CHAPTER 6: SETPOINTS
BLOCK NTRL TOC Shot 1 to 4
Range: Off/On
Default: Off
If set to “On” for the selected shot, the operation of the element will initiate a breaker trip
after the corresponding breaker reclosing shot.