CHAPTER 6: SETPOINTS S4 CONTROLS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6–151
Figure 6-63: Second harmonic inhibit logic diagram
LED: PICKUP
SETPOINT
FUNCTION :
Disabled = 0
Alarm
Latched Alarm
Control
OR
SETPOINT
2nd HRMC PICKUP :
HM2A PICKUP
RUN
SETPOINT
2nd HRMC DELAY :
t
PKP
0
Hrmc 2nd OP
Hrmc 2nd PKP
AND AND
Command
RESET
OR
LED: ALARM
SETPOINT
MINIMUM OPER
CURRENT :
IA MINIMUM
RUN
S
LATCH
Set-
Dominant
R
Phase A Current (IA)
Phase B Current (IB)
Phase C Current (IC)
Phase A HM 2nd (HM 2A)
Phase B HM 2nd (HM 2B)
Phase C HM 2nd (HM2C)
IB MINIMUM
IC MINIMUM
HM2B PICKUP
RUN
HM2C PICKUP
RUN
SETPOINT
OUTPUT RELAY X
Average HM 2nd (HM2avg )
Average Current (Iavg)
Iavg MINIMUM
HM2avg PICKUP
RUN
SETPOINT
PHASES FOR
OPERATION :
ANY ONE : At least one
phase picked up ;
ANY TWO: Two or more
phases picked up;
ALL THREE: All three
phases picked up;
AVERAGE: Average value
picked up.
Phase Currents
Second Harmonic Ratios
Message
Event Recorder
Transient Recorder
Message
Event Recorder
Transient Recorder
Do Not Operate, Operate
898855A1.cdr