6–164 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
S5 INPUTS/OUTPUTS CHAPTER 6: SETPOINTS
1. Output Relay 7 will be de-energized, if the relay is not IN-SERVICE or the control power
is not applied to the relay
2. Output Relay 7 will be energized when the control power is applied to the relay and
the relay is IN-SERVICE mode.
3. Output Relay 7 will stay de-energized, when the control power is applied, if the relay
was not programmed as “Ready”, or upon major self-test failure during relay boot up.
4. Output Relay 7 will change state from energized to de-energized if the 350 relay
experiences any major self-test failure.