EasyManua.ls Logo

GE 845 - Page 197

GE 845
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4: SETPOINTS DEVICE
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–69
REMOTE IO DETECT VALUE
Range: Up to 6 alphanumeric characters
Shows the letter type of the Remote RTD card Board ID installed (e.g. GGGG).
CURRENT CUTOFF
Range: 0.000 to 1.000 p.u. in steps of 0.001 p.u.
Default: 0.020 p.u.
VOLTAGE CUTOFF
Range: 0.0 to 300.0 in steps of 0.1 V
Default: 1.0 V
FAST PATH:
Lower the Voltage Cutoff and Current Cutoff levels with care as the relay accepts lower
signals as valid measurements. Unless dictated otherwise by a specific application, the
default settings of “0.020 pu” for current and “1.0 V” for voltage are recommended.”

Table of Contents

Related product manuals