EasyManua.ls Logo

GE 845 - Undervoltage Curves

GE 845
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4: SETPOINTS PROTECTION
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–199
Undervoltage Curves The undervoltage elements can be programmed to have an inverse time delay
characteristic. The undervoltage delay setpoint defines a family of curves as shown below.
The operating time is given by:
T = D/(1 - V/V
pkp
)
Where:
T = Operating Time
D = Undervoltage Pickup Time Delay setpoint (for D = 0.00 operates instantaneously)
V = Voltage as a fraction of the nominal VT Secondary Voltage
V
pkp
= Undervoltage Pickup Level
The element resets instantaneously if the applied voltage exceeds the dropout voltage. The
delay setting selects the minimum operating time of the phase undervoltage.
NOTE
NOTE:
At 0% of Pickup, the operating time equals the Undervoltage Pickup Time Delay setpoint.
Figure 4-72: Inverse Time Undervoltage Curves
If FlexCurves are selected, the operating time determined based on following equation:
T= Flexcurve (V
pkp
/ V)
NOTE
NOTE:
FlexCurve reverses the ratio of voltages. The ratio of set pickup value to the measured
voltage.
Example: For a Pickup set to 0.9 x VT, when the measured voltage is 0.82 x VT, the ratio
would be 0.9/0.8 = 1.1, therefore in the FlexCurve, the corresponding Trip time setting entry
is at 1.1 x PKP (not at 0.82 x PKP). On the other hand, when the measured voltage is 1 x VT,
the ratio is 0.9/1 = 0.9, therefore, in the FlexCurve, the corresponding Reset time entry is at
0.9 x PKP.

Table of Contents

Related product manuals