CHAPTER 4: SETPOINTS SYSTEM
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–101
Figure 4-28: Transformer Status Detection Logic Diagram
894009A2.cdr
AND
SETPOINT METERING
W1/2/3 PHASE
CURRENTS
W1 Ia
W1 Ic
W1 Ib
W2 Ia
W2 Ic
W2 Ib
W3 Ia
W3 Ic
W3 Ib
MINIMUM CURRENT
W1 Ia < Minimum
W1 Ic < Minimum
W1 Ib < Minimum
W2 Ia < Minimum
W2 Ic < Minimum
W2 Ib < Minimum
W3 Ia < Minimum
W3 Ic < Minimum
W3 Ib < Minimum
METERING
PHASE VOLTAGE (J2)
Vab
Vca
Vbc
SETPOINT
MINIMUM VOLTAGE
V < Minimum
V < Minimum
V < Minimum
AND
OR
SENSING BY BREAKERS
OPEN
FlexLogic Operand
XFMR De-Energized
FlexLogic Operand
XFMR Energized
ANDAND
ALL BREAKERS OPEN
AND
Disabled = 0 Enabled =1
SETPOINT
SENSING BY VOLTAGE
Disabled = 0, Enabled = 1
RUN
SETPOINT
CURRENT SUPERVISION
RUN
SETPOINT
Disabled = 0, Enabled = 1
AND AND
LED: DE-ENERGIZED
SETPOINT
FlexLogic operand
FlexLogic Operand
Not Configured
NO R
AND
PKP
t = 50ms