CHAPTER 4: SETPOINTS PROTECTION
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–187
Figure 4-64: Ground Directional Overcurrent Protection logic diagram
894158A1.cdr
POLARIZING VOLTAGE :
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
GROUND
FUNCTION :
DIR OC
BLOCK :
GROUND
LIMIT ANGLE :
DIR OC FWD
GROUND
ECA:
DIR OC FWD
GROUND
LIMIT ANGLE :
DIR OC REV
GROUND DIR OC FWD
PICKUP :
GROUND
PICKUP :
DIR OC REV
Gnd Dir OC FWD
Gnd Dir OC REV
Disabled =0
Measured VX
Calculated V _ 0
}
Ground Current (Ig)
Off=0
Enabled =1
AND
AND
AND
AND
AND
Ig PICKUP
Ig PICKUP
Voltage Polarization
-3V_0
Ig
FWD
FWD
REV
REV
RUN
RUN
RUN
1.25 cy
1.5 cy
TO GROUND TOC AND
IOC ELEMENTS
TO GROUND TOC AND
IOC ELEMENTS
AND
SETPOINT
SIGNAL INPUT :
CT Bank 1 – J1