EasyManua.ls Logo

GE 845 - Page 356

GE 845
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4–228 845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
Figure 4-87: Directional Power logic diagram
LED: PICKUP
Three - phase Power
Real Power (P)
Reactive Power (Q)
SETPOINTS
BLOCK :
Off=0
AND
SETPOINTS
DIR POWER 1
FUNCTION :
Disabled
Trip
Alarm
Latched Alarm
Configurable
OR
SETPOINTS
DIR POWER 1
RCA :
DIRECTIONAL POWER
CHARACTERISTICS
SETPOINTS
DIR POWER 1
STAGE 1 DELAY:
t
PKP
100 ms
FlexLogic Operands
DirPwr 1 Stg2 PKP
AN D AND AND
Command
RESET
OR
LED: ALARM
LED: TRIP
Operate Output Relay 1 (TRIP)
RUN
SETPOINTS
RELAYS
Do Not Operate , Operate
DIR POWER 1
CALIBRATION :
DIR POWER 1
STAGE 1 SMIN :
DIR POWER 1
STAGE 2 SMIN :
SETPOINTS
DIR POWER 1
STAGE 2 DELAY :
t
PKP
100 ms
DirPwr 1 Stg1 PKP
DirPwr 1 Stg1 OP
DirPwr 1 Stg2 OP
DirPwr 1 PKP
OR
OR
DirPwr 1 OP
S
LATCH
Set-
Dominant
R
89$
.cdr

Table of Contents

Related product manuals