EasyManua.ls Logo

GE 845 - Page 389

GE 845
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 4: SETPOINTS MONITORING
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–261
Figure 4-106: Breaker Arcing Current logic diagram
SETPOINTS
BKR 1 ARCING
FUNCTION :
Alarm
Latched Alarm
OR
AND
LED: ALARM /
LATCHED ALARM
Command
AND
S
R
LATCH # 1
Set-
Dominant
Configurable
FlexLogic Operands
BKR 1 Arc OP
SETPOINTS
Do Not Operate, Operate
OUTPUT RELAY 3 (X)
CT Bank current IB
CT Bank current IC
AND
SETPOINTS
BKR 1 ARCING
BLOCK :
Off = 0
CT Bank current IA
Disabled
AND
COMMAND
CLEAR BKR 1 ARCING
CURRENT :
YES = 1
OR
RESET
IA
²
t Integrate
IB
²
t Integrate
IC
²
t Integrate
RUN
RUN
RUN
SETPOINTS
BKR 1 ARCING
DELAY:
t
delay
0
BKR 1 ARCING
INITIATION:
Off = 0
SETPOINTS
OR
100ms
0
IA
²
cycle
IB
²
cycle
IC
²
cycle
Add to accumulator
Set all to 0
Select highest value
BKR 1 ARCING
CURRENTS
RECORDS
SETPOINTS
BKR 1 ARCING
ALARM LEVEL :
kA
²
cyc > Alarm Level
NO = 0
Total I
²
cycle
892743A2.cdr

Table of Contents

Related product manuals