CHAPTER 4: SETPOINTS FLEXLOGIC
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–337
Ground Directional OC Gnd Dir OC FWD  
Gnd Dir OC REV 
Ground directional overcurrent forward has operated  
Ground directional overcurrent reverse has operated 
Harmonic Detection Harm Det 1 PKP  
Harm Det 1 OP  
Harmonic Detection 2 to 6 
Harmonic Detection 1 has picked up  
Harmonic Detection 1 has operated  
The same set of operands as per Harmonic Detection 1 
Harmonic Derating W1 Harm Derat PKP  
W1 Harm Derat OP  
W2 Harm Derat PKP  
W2 Harm Derat OP  
W3 Harm Derat PKP  
W3 Harm Derat OP  
Load Limit Reduced 
Harmonic Derating W1 has picked up  
Harmonic Derating W1 has operated  
Harmonic Derating W2 has picked up  
Harmonic Derating W2 has operated  
Harmonic Derating W3 has picked up  
Harmonic Derating W3 has operated  
Harmonic Derating has detected load limit reduced 
Hottest Spot Hottest-Spot PKP  
Hottest-Spot OP 
The Hottest-spot temperature element has picked up  
The Hottest-spot temperature element has operated 
Local Control Mode SBO Enabled  
Local Mode ON 
 Local Mode OFF  
BKR[X] Local Open  
BKR[X] Local Close  
BKR[X] Loc Blk Open  
BKR[X] Loc Blk Close  
BKR[X] Loc Blk Open By  
BKR[X] Loc Blk Cls By  
BKR[X] Tag On  
BKR[X] Tag Off  
BKR[X] Selected  
SW[X] Local Open  
SW[X] Local Close  
SW[X] Loc Blk Open  
SW[X] Loc Blk Close 
 SW[X] Loc Blk Open By  
SW[X] Loc Blk Cls By  
SW[X] Tag On  
SW[X] Tag Off  
SW[X] Selected 
Select Before Operate control mode is enabled  
Local mode is ON (shows LM in display banner)  
Local mode is OFF  
Local Open command has been initiated to BKR[X]  
Local Close command has been initiated to BKR[X]  
Open command to BKR[X] is blocked  
Close command to BKR[X] is blocked  
Open command to BKR[X] is permitted, Block Open signal is bypassed  
command to BKR[X] is permitted, Block Close signal is bypassed  
The selected breaker is tagged  
The selected breaker is untagged  
Breaker BKR[X] has been selected in SLD  
Local Open command has been initiated to SW[X]  
Local Close command has been initiated to SW[X]  
Open command to the switch is blocked  
Close command to the switch is blocked  
Open switch command is permitted, Block Open signal is bypassed  
Close switch command is permitted, Block Close signal is bypassed 
 The selected breaker/switch is tagged  
The selected breaker/switch is untagged  
Disconnect Switch 1(8) has been selected in SLD  
[X] - the element number.
Loss of 
Communications
Loss Of Comms PKP  
Loss Of Comms OP
Loss Of Comms has picked up  
Loss Of Comms has operated
Neutral TOC Ntrl TOC 1 PKP  
Ntrl TOC 1 OP  
Neutral TOC 2  
Neutral TOC 2, Neutral TOC 3 
Neutral time overcurrent 1 has picked up  
Neutral time overcurrent 1 has operated  
The same set of operands as per Neutral TOC 1 
Neutral IOC Ntrl IOC 1 PKP  
Ntrl IOC 1 OP  
Ntrl IOC 2  
Neutral IOC 2 to Neutral IOC6 
Neutral IOC 1 has picked up  
Neutral IOC 1 has operated  
The same set of operands as per Neutral IOC 1 
Neutral Directional OC Ntrl Dir OC FWD  
Ntrl Dir OC REV 
Neutral directional overcurrent forward has operated  
Neutral directional overcurrent reverse has operated 
Neutral OV Ntrl OV 1 PKP  
Ntrl OV 1 OP 
Neutral overvoltage element 1 has picked up  
Neutral overvoltage element 1 has operated 
Negative sequence OV NegSeq OV 1 PKP  
NegSeq OV 1 OP 
Negative-sequence overvoltage element 1 has picked up  
Negative-sequence overvoltage element 1 has operated 
Negative Sequence TOC NegSeq TOC 1 PKP  
NegSeq TOC 1 OP  
Neg Seq TOC 2, Neg Seq TOC 3 
Negative Sequence TOC 1 has picked up  
Negative Sequence TOC 1 has operated  
Same set of operands as shown for Negative Sequence TOC 1 
Negative Sequence IOC NegSeq IOC 1 PKP  
NegSeq IOC 1 OP  
Neg Seq IOC 2, Neg Seq IOC 3 
Negative Sequence IOC has picked up  
Negative Sequence IOC 1 has operated  
Same set of operands as shown for Negative Sequence IOC 1 
Negative Sequence 
Directional OC
NegSeq DirOC FWD  
NegSeq DirOC REV 
Negative Sequence directional overcurrent forward has operated  
Negative Sequence directional overcurrent reverse has operated 
ELEMENT OPERANDS EVENT DESCRIPTION