CHAPTER 4: SETPOINTS FLEXLOGIC
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–339
Phase Directional OC Ph Dir OC REV A  
Ph Dir OC REV B  
Ph Dir OC REV C  
Ph Dir OC REV 
Phase A current in reverse direction  
Phase B current in reverse direction  
Phase C current in reverse direction  
At least one phase current in reverse direction 
Phase UV Ph UV 1 PKP  
Ph UV 1 PKP A  
Ph UV 1 PKP B  
Ph UV 1 PKP C  
Ph UV 1 OP  
Ph UV 1 OP A  
Ph UV 1 OP B  
Ph UV 1 OP C  
Ph UV 2 
At least one phase of phase undervoltage 1 has picked up  
Phase A of phase undervoltage 1 has picked up  
Phase B of phase undervoltage 1 has picked up  
Phase C of phase undervoltage 1 has picked up  
At least one phase of phase undervoltage 1 has operated  
Phase A of phase undervoltage 1 has operated  
Phase B of phase undervoltage 1 has operated  
Phase C of phase undervoltage 1 has operated  
The same set of operands as per Phase UV 1 
Phase OV Ph OV 1 PKP  
Ph OV 1 PKP A  
Ph OV 1 PKP B  
Ph OV 1 PKP C  
Ph OV 1 OP  
Ph OV 1 OP A  
Ph OV 1 OP B  
Ph OV 1 OP C  
Ph OV 2 
At least one phase of phase overvoltage 1 has picked up  
Phase A of phase overvoltage element 1 has picked up  
Phase B of phase overvoltage element 1 has picked up  
Phase C of phase overvoltage element 1 has picked up  
At least one phase of phase overvoltage 1 has operated  
Phase A of phase overvoltage element 1 has operated  
Phase B of phase overvoltage element 1 has operated  
Phase C of phase overvoltage element 1 has operated  
The same set of operands as per Phase OV 1 
Power Factor PF 1 Switch-In  
PF 1 Switch-Out  
PF 1 Switch-In OP  
PF 1 Switch-Out OP  
PF 2 
The measured power factor has crossed the Switch-in setpoint  
The measured power factor has crossed the Switch-Out setpoint  
The PF1 Switch-In element operated  
The PF1 Switch-Out element operated  
The same set of operands as per PF 1 
Programmable 
Pushbuttons
PB 1 ON  
PB 1 OFF  
Pushbuttons 2 and 3 
Pushbutton 1 ON state has been asserted  
Pushbutton 1 OFF state has been asserted  
The same set of operands as shown for Pushbutton 1 
Pulse Output Pos Wthrs Pulse OP  
 
Neg Wthrs Pulse OP  
 
Pos Varh Pulse OP  
 
Neg Varh Pulse OP 
Positive Watthours pulse occurs at the end of the programed energy 
increment  
Negative Watthours pulse occurs at the end of the programed energy 
increment  
Positive VARhours pulse occurs at the end of the programed energy 
increment  
Negative VARhours pulse occurs at the end of the programed energy 
increment 
Relay Service In-Service  The relay is In-Service 
Remote Input Rem Ip # ON  
Rem Ip # OFF 
# – any remote input number 
Remote Modbus Device FlexLogic Operand [X] On  
FlexLogic Operand [X] Off 
[X] - the element number. Note the operand name will change depending 
on what is programmed.
Resetting Reset OP  
Reset OP (PB)  
Reset OP (Operand)  
Reset OP (Comms) 
Reset command  
Reset command initiated from a front panel pushbutton  
Reset command initiated from a FlexLogic operand  
Reset command initiated via communications 
Restricted Ground Fault RGF 1 PKP  
RGF 1 OP  
RGF 1 Superv ON  
RGF 2 and RGF 3 
Restricted Ground Fault 1 has picked up  
Restricted Ground Fault 1 has operated  
The Restricted Ground Fault supervision has operated  
Same set of operands as for RGF1 
RTD Temperature RTD 1 Trip PKP  
 
RTD 1 Trip OP  
 
RTD 1 Alarm PKP  
RTD 1 Alarm OP  
RTD 1 Open  
RTD 1 Shorted 
RTD 1 Trip has picked up. It is displayed as “RTD 1 PKP” if the Trip Function 
is set to “Configurable”.  
RTD 1 Trip has operated. It is displayed as “RTD 1 OP” if the Trip Function is 
set to “Configurable”.  
RTD 1 Alarm has picked up  
RTD 1 Alarm has operated  
RTD 1 sensor is detected open  
RTD 1 sensor is detected shorted 
RTD 2 to RTD 12 Similar to RTD 1
Hot RTD  Any RTD Alarm PKP operand has picked up. 
RTD Trouble RTD Trouble PKP  
RTD Trouble OP 
RTD Trouble has picked up  
RTD Trouble has operated 
ELEMENT OPERANDS EVENT DESCRIPTION