2-80 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 60E7 87PC Scheme Signal 0 to 2 --- 1 F150 0 (MIXED I_2
- K*I_1)
" 60E8 87PC Signal Source 0 to 1 --- 1 F089 0 (One
Source
Current)
" 60E9 87PC FDL Pickup 0.02 to 15 pu 0.01 F001 50
" 60EB 87PC FDH Pickup 0.05 to 15 pu 0.01 F001 75
" 60EC 87PC Mixed Signal K 0 to 0.25 --- 0.01 F001 20
" 60F0 87PC Phase Delay Ch1 0 to 30 ms 0.1 F001 0
" 60F2 87PC Phase Delay Ch2 0 to 30 ms 0.1 F001 0
" 60F8 87PC Transient Pickup 0 to 65.535 s 0.001 F001 30
" 60FD 87PC Asymmetry Channel 1 -5 to 5 ms 0.1 F002 0
" 6104 87PC Asymmetry Channel 2 -5 to 5 ms 0.1 F002 0
" 6106 87PC Stability Angle 40 to 140 degrees 5 F001 75
" 6107 87PC Transient Reset 0 to 65.535 s 0.001 F001 30
" 6108 87PC Received Volts Channel 1 0 to 125 V 0.1 F001 120
" 6109 87PC Received Volts Channel 2 0 to 125 V 0.1 F001 120
" 610A 87PC High-Speed Contact 1 0 to 64 --- 1 F490 0
" 610B 87PC High-Speed Contact 2 0 to 64 --- 1 F490 0
" 610C 87PC FDL AUX 0 to 4294967295 --- 1 F300 0
" 610E 87PC FDH AUX 0 to 4294967295 --- 1 F300 0
" 6110 87PC Reset Delay 0 to 200 ms 1 F001 30
" 6111 87PC Mixed Signal Reference Angle 0 to 359 ° 1 F001 0
" 6112 87PC Trip Security 0 to 1 --- 1 F534 0 (First
Coincidence)
" 6113 87PC Second Coincidence Timer 10 to 200 ms 1 F001 40
" 6114 87PC Enhanced Stability Angle 40 to 180 ° 5 F001 110
" 6115 87PC FDH Supervision 0 to 4294967295 --- 1 F300 0
" 6117 87PC Pickup Delay 0 to 50 ms 1 F001 0
" 6118 87PC Stop Tx 0 to 4294967295 --- 1 F300 0
" 611A 87PC Tx Reset Delay 0 to 1000 ms 1 F001 0
Continuous Monitor (Read/Write Setting)
L90 6130 Continuous Monitor Function 0 to 1 --- 1 F102 0 (Disabled)
" 6131 Continuous Monitor I (current) OP 0 to 4294967295 --- 1 F300 0
" 6133 Continuous Monitor I (current) Supervision 0 to 4294967295 --- 1 F300 0
" 6135 Continuous Monitor V (voltage) OP 0 to 4294967295 --- 1 F300 0
" 6137 Continuous Monitor V (voltage) Supervision 0 to 4294967295 --- 1 F300 0
" 6139 Continuous Monitor Target 0 to 2 --- 1 F109 0 (Self-reset)
" 613A Continuous Monitor Events 0 to 1 --- 1 F102 0 (Disabled)
Transformer Hottest Spot (Read/Write Grouped Setting)
G30, T35, T60 6140 Transformer Hottest Spot Function 0 to 1 --- 1 F102 0 (Disabled)
" 6141 Transformer Hottest Spot Pickup 50 to 300 °C 1 F001 140
" 6142 Transformer Hottest Spot Delay 0 to 30000 min 1 F001 1
" 6143 Transformer Hottest Spot Block 0 to 4294967295 --- 1 F300 0
" 6145 Transformer Hottest Spot Target 0 to 2 --- 1 F109 0 (Self-reset)
" 6146 Transformer Hottest Spot Events 0 to 1 --- 1 F102 0 (Disabled)
Transformer Aging Factor (Read/Write Grouped Setting)
G30, T35, T60 6150 Transformer Aging Factor Function 0 to 1 --- 1 F102 0 (Disabled)
Products Address Register name Range Units Step Format Default