3-188 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.6 General (Gen) logical device
The Ctrl logical device contains logical nodes that model UR FlexLogic, Virtual Outputs, non-volatile latches, FlexElements,
and recording (for example, oscillography) functions.
The Ctrl logical device is available when the Advanced IEC 61850 option is purchased with the UR device.
phsθHar(0)
.instCVal
Vector MX R
phsθHar(0)
.instCVal.mag.f
FLOAT32 0 R
phsθHar(0).cVal Vector MX R
phsθHar(0).cVal
.mag.f
FLOAT32 0 R
phsθHar(0).units Unit CF R
phsθHar(0).units
.SIUnit
ENUMERATED 1, the code for dimensionless
(percentage)
R
phsθHar(0).units
.multiplier
ENUMERATED -2 R
phsθHar(0).db INT32U CF 0 R
phsθHar(0).zeroDb INT32U CF 0 R
phsθHar(1) CMV R
phsθHar(1)
.instCVal
Vector MX R
phsθHar(1)
.instCVal.mag.f
FLOAT32 0 R
phsθHar(1).cVal Vector MX R
phsθHar(1).cVal
.mag.f
FLOAT32 0 R
phsθHar(1).units Unit CF R
phsθHar(1).units
.SIUnit
ENUMERATED 1, the code for dimensionless
(percentage)
R
phsθHar(1).units
.multiplier
ENUMERATED -2 R
phsθHar(1).db INT32U CF 0 R
phsθHar(1).zeroDb INT32U CF 0 R
phsθHar(n) CMV R
phsθHar(n)
.instCVal
Vector MX R
phsθHar(n)
.instCVal.mag.f
FLOAT32 SRC # nτ Vφ R
phsθHar(n).cVal Vector MX R
phsθHar(n).cVal
.mag.f
FLOAT32 SRC # nτ Vφ magnitude, with
dead band
R
phsθHar(n).units Unit CF R
phsθHar(n).units
.SIUnit
ENUMERATED 1, the code for dimensionless
(percentage)
R
phsθHar(n).units
.multiplier
ENUMERATED -2 R
phsθHar(n).db INT32U CF HThdMHAI#.HPhV.phsθHar(n).db R/W/C
phsθHar(n).zeroDb INT32U CF 0 R
numHar INT16U CF 25 R
numCyc INT16U CF 1 R
evalTm INT16U CF (1/ NOMINAL FREQUENCY) *
1000
R
frequency FLOAT32 CF NOMINAL FREQUENCY R
rmsCyc INT16U CF 1 R
LNName: HThdMHAI# LDevice inst: Meter UR element: Harmonics and THD metering
data obj. data attribute Type FC UR Name Description R/W/C