CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-187
3
phsθHar(0).units
.SIUnit
ENUMERATED 1, the code for dimensionless
(percentage)
R
phsθHar(0).units
.multiplier
ENUMERATED -2 R
phsθHar(0).db INT32U CF 0 R
phsθHar(0).zeroDb INT32U CF 0 R
phsθHar(1) CMV R
phsθHar(1)
.instCVal
Vector MX R
phsθHar(1)
.instCVal.mag.f
FLOAT32 0 R
phsθHar(1).cVal Vector MX R
phsθHar(1).cVal
.mag.f
FLOAT32 0 R
phsθHar(1).units Unit CF R
phsθHar(1).units
.SIUnit
ENUMERATED 1, the code for dimensionless
(percentage)
R
phsθHar(1).units
.multiplier
ENUMERATED -2 R
phsθHar(1).db INT32U CF 0 R
phsθHar(1).zeroDb INT32U CF 0 R
phsθHar(n) CMV R
phsθHar(n)
.instCVal
Vector MX R
phsθHar(n)
.instCVal.mag.f
FLOAT32 SRC # nτ Iφ R
phsθHar(n).cVal Vector MX R
phsθHar(n).cVal
.mag.f
FLOAT32 SRC # nτ Iφ magnitude, with
dead band
R
phsθHar(n).units Unit CF
R
phsθHar(n).units
.SIUnit
ENUMERATED 1, the code for dimensionless
(percentage)
R
phsθHar(n).units
.multiplier
ENUMERATED -2 R
phsθHar(n).db INT32U CF HThdMHAI#.HA.phsθHar(n).db R/W/C
phsθHar(n).zeroDb INT32U CF 0 R
numHar INT16U CF 25 R
numCyc INT16U CF 1 R
evalTm INT16U CF (1/ NOMINAL FREQUENCY) *
1000
R
frequency FLOAT32 CF NOMINAL FREQUENCY R
rmsCyc INT16U CF 1 R
ThdPhV WYE Instantiated only in products that
measure THD voltage
R
phsθ CMV R
phsθ.instCVal Vector MX R
phsθ.instCVal.mag
.f
FLOAT32 SRC # THD Vφ magnitude R
phsθ.cVal Vector MX R
phsθ.cVal.mag.f FLOAT32 SRC # THD Vφ magnitude, with
dead band
R
phsθ.units Unit CF R
phsθ.units.SIUnit ENUMERATED 1, the code for dimensionless
(percentage)
R
phsθ.units
.multiplier
ENUMERATED -2 R
phsθ.db INT32U CF HThdMHAI#.ThdPhV.phsθ.db R/W/C
phsθ.zeroDb INT32U CF 0 R
HPhV HWYE Instantiated only in products that
measure voltage harmonics
R
phsθHar(0) CMV R
LNName: HThdMHAI# LDevice inst: Meter UR element: Harmonics and THD metering