2-82 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
Transformer Instantaneous Differential (Read/Write Grouped Setting)
T35, T60 61DA Inst Differential Function 0 to 1 --- 1 F102 0 (Disabled)
" 61DB Inst Differential Pickup 2 to 30 pu 0.001 F001 8000
" 61DC Inst Differential Block 0 to 4294967295 --- 1 F300 0
" 61DE Inst Differential Target 0 to 2 --- 1 F109 0 (Self-reset)
" 61DF Inst Differential Events 0 to 1 --- 1 F102 0 (Disabled)
Autoreclose (Read/Write Setting) (1, 4, or 6 Modules)
D30, F35, F60,
L30
6200 Autoreclose 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 6201 Autoreclose 1 Initiate 0 to 4294967295 --- 1 F300 0
" 6203 Autoreclose 1 Block 0 to 4294967295 --- 1 F300 0
" 6205 Autoreclose 1 Max Number of Shots 1 to 4 --- 1 F001 1
" 6206 Autoreclose 1 Manual Close 0 to 4294967295 --- 1 F300 0
" 6208 Autoreclose 1 Manual Reset from LO 0 to 4294967295 --- 1 F300 0
" 620A Autoreclose 1 Reset Lockout if Breaker
Closed
0 to 1 --- 1 F108 0 (Off)
" 620B Autoreclose 1 Reset Lockout On Manual
Close
0 to 1 --- 1 F108 0 (Off)
" 620C Autoreclose 1 Breaker Closed 0 to 4294967295 --- 1 F300 0
" 620E Autoreclose 1 Breaker Open 0 to 4294967295 --- 1 F300 0
" 6210 Autoreclose 1 Block Time Upon Manual
Close
0 to 655.35 s 0.01 F001 1000
" 6211 Autoreclose 1 Dead Time Shot 1 0 to 655.35 s 0.01 F001 100
" 6212 Autoreclose 1 Dead Time Shot 2 0 to 655.35 s 0.01 F001 200
" 6213 Autoreclose 1 Dead Time Shot 3 0 to 655.35 s 0.01 F001 300
" 6214 Autoreclose 1 Dead Time Shot 4 0 to 655.35 s 0.01 F001 400
" 6215 Autoreclose 1 Reset Lockout Delay 0 to 655.35 s 0.01 F001 6000
" 6216 Autoreclose 1 Reset Time 0 to 655.35 s 0.01 F001 6000
" 6217 Autoreclose 1 Incomplete Sequence Time 0 to 655.35 s 0.01 F001 500
" 6218 Autoreclose 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 6219 Autoreclose 1 Reduce Max 1 0 to 4294967295 --- 1 F300 0
" 621B Autoreclose 1 Reduce Max 2 0 to 4294967295 --- 1 F300 0
" 621D Autoreclose 1 Reduce Max 3 0 to 4294967295 --- 1 F300 0
" 621F Autoreclose 1 Add Delay 1 0 to 4294967295 --- 1 F300 0
" 6221 Autoreclose 1 Delay 1 0 to 655.35 s 0.01 F001 0
" 6222 Autoreclose 1 Add Delay 2 0 to 4294967295 --- 1 F300 0
" 6224 Autoreclose 1 Delay 2 0 to 655.35 s 0.01 F001 0
" 6225 Reserved (4 items) 0 to 0.001 --- 0.001 F001 0
F35, F60 6229 ...Repeated for Autoreclose 2
" 6252 ...Repeated for Autoreclose 3
" 627B ...Repeated for Autoreclose 4
F35 62A4 ...Repeated for Autoreclose 5
" 62CD ...Repeated for Autoreclose 6
Negative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 or 3 Modules)
C70, D30, D60,
F35, F60, L30,
L60, L90, T60
6300 Negative Sequence Time Overcurrent 1
Function
0 to 1 --- 1 F102 0 (Disabled)
" 6301 Negative Sequence Time Overcurrent 1
Signal Source
0 to 5 --- 1 F167 0 (SRC 1)
Products Address Register name Range Units Step Format Default