CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-103
2
VT Terminal Settings (Read/Write Setting) (12 Modules)
B90 6F9C Terminal Voltage 1 Ratio 1 to 24000 :1 0.01 F060 1
" 6F9E Terminal Voltage 1 Secondary 50 to 240 V 0.1 F001 664
" 6F9F ...Repeated for Terminal Voltage 2
" 6FA2 ...Repeated for Terminal Voltage 3
" 6FA5 ...Repeated for Terminal Voltage 4
" 6FA8 ...Repeated for Terminal Voltage 5
" 6FAB ...Repeated for Terminal Voltage 6
" 6FAE ...Repeated for Terminal Voltage 7
" 6FB1 ...Repeated for Terminal Voltage 8
" 6FB4 ...Repeated for Terminal Voltage 9
" 6FB7 ...Repeated for Terminal Voltage 10
" 6FBA ...Repeated for Terminal Voltage 11
" 6FBD ...Repeated for Terminal Voltage 12
B90 Function (Read/Write Setting)
B90 6FC0 B90 Function 0 to 1 --- 1 F250 1
(Protection)
Terminal Frequency (Read Only)
B90 6FD0 Terminal Frequency 2 to 90 Hz 0.01 F001 0
" 6FD1 Terminal Tracking Frequency 2 to 90 Hz 0.01 F001 0
Breaker Failure Current Supervision (Read/Write Grouped Setting) (24 Modules)
B90 7000 Breaker Failure 1 Current Supervision
Function
0 to 1 --- 1 F102 0 (Disabled)
" 7001 Breaker Failure 1 Current Supervision CT 0 to 23 --- 1 F400 0
" 7002 Breaker Failure 1 Current Supervision Amp
Supv Pickup
0.02 to 30 pu 0.001 F001 1050
" 7003 Breaker Failure 1 Current Supervision Amp
Hiset Pickup
0.02 to 30 pu 0.001 F001 1050
" 7004 Breaker Failure 1 Current Supervision Amp
Loset Pickup
0.02 to 30 pu 0.001 F001 1050
" 7005 Reserved (4 items) 0 to 65535 --- 1 F001 0
" 7009 ...Repeated for Breaker Failure 2
" 7012 ...Repeated for Breaker Failure 3
" 701B ...Repeated for Breaker Failure 4
" 7024 ...Repeated for Breaker Failure 5
" 702D ...Repeated for Breaker Failure 6
" 7036 ...Repeated for Breaker Failure 7
" 703F ...Repeated for Breaker Failure 8
" 7048 ...Repeated for Breaker Failure 9
" 7051 ...Repeated for Breaker Failure 10
" 705A ...Repeated for Breaker Failure 11
" 7063 ...Repeated for Breaker Failure 12
" 706C ...Repeated for Breaker Failure 13
" 7075 ...Repeated for Breaker Failure 14
" 707E ...Repeated for Breaker Failure 15
" 7087 ...Repeated for Breaker Failure 16
" 7090 ...Repeated for Breaker Failure 17
" 7099 ...Repeated for Breaker Failure 18
Products Address Register name Range Units Step Format Default