2-106 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 7125 Breaker Failure 1 Retrip Time Delay 0 to 65.535 s 0.001 F001 0
" 7126 Breaker Failure 1 Block 0 to 4294967295 --- 1 F300 0
" 7128 Breaker Failure 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 7129 Breaker Failure 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 712A Reserved (6 items) 0 to 65535 --- 1 F001 0
" 7130 ...Repeated for Breaker Failure 2
" 7160 ...Repeated for Breaker Failure 3
" 7190 ...Repeated for Breaker Failure 4
" 71C0 ...Repeated for Breaker Failure 5
" 71F0 ...Repeated for Breaker Failure 6
" 7220 ...Repeated for Breaker Failure 7
" 7250 ...Repeated for Breaker Failure 8
" 7280 ...Repeated for Breaker Failure 9
" 72B0 ...Repeated for Breaker Failure 10
" 72E0 ...Repeated for Breaker Failure 11
" 7310 ...Repeated for Breaker Failure 12
" 7340 ...Repeated for Breaker Failure 13
" 7370 ...Repeated for Breaker Failure 14
" 73A0 ...Repeated for Breaker Failure 15
" 73D0 ...Repeated for Breaker Failure 16
" 7400 ...Repeated for Breaker Failure 17
" 7430 ...Repeated for Breaker Failure 18
" 7460 ...Repeated for Breaker Failure 19
" 7490 ...Repeated for Breaker Failure 20
" 74C0 ...Repeated for Breaker Failure 21
" 74F0 ...Repeated for Breaker Failure 22
" 7520 ...Repeated for Breaker Failure 23
" 7550 ...Repeated for Breaker Failure 24
Ground Distance (Read/Write Grouped Setting) (3 or 5 Modules)
D30, D60, L60, 
L90, T60
7130 Ground Distance Zone 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 7131 Ground Distance Zone 1 Current 
Supervision
0.05 to 30 pu 0.001 F001 200
" 7132 Ground Distance Zone 1 Reach 0.02 to 500 ohms 0.01 F001 200
" 7133 Ground Distance Zone 1 Direction 0 to 2 --- 1 F154 0 (Forward)
" 7134 Ground Distance Zone 1 Comparator Limit 30 to 90 degrees 1 F001 90
" 7135 Ground Distance Zone 1 Delay 0 to 65.535 s 0.001 F001 0
" 7136 Ground Distance Zone 1 Block 0 to 4294967295 --- 1 F300 0
" 7138 Ground Distance Zone 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 7139 Ground Distance Zone 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 713A Ground Distance Zone 1 Shape 0 to 1 --- 1 F120 0 (Mho)
" 713B Ground Distance Zone 1 Z0 Z1 Magnitude 0 to 10 --- 0.01 F001 270
" 713C Ground Distance Zone 1 Z0 Z1 Angle -90 to 90 degrees 1 F002 0
" 713D Ground Distance Zone 1 RCA 30 to 90 degrees 1 F001 85
" 713E Ground Distance Zone 1 DIR RCA 30 to 90 degrees 1 F001 85
" 713F Ground Distance Zone 1 DIR Comp Limit 30 to 90 degrees 1 F001 90
" 7140 Ground Distance Zone 1 Quad Right Blinder 0.02 to 500 ohms 0.01 F001 1000
Products Address Register name Range Units Step Format Default