2-126 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" 859A ...Repeated for Direct Integer Output 10
" 85A4 ...Repeated for Direct Integer Output 11
" 85AE ...Repeated for Direct Integer Output 12
" 85B8 ...Repeated for Direct Integer Output 13
" 85C2 ...Repeated for Direct Integer Output 14
" 85CC ...Repeated for Direct Integer Output 15
" 85D6 ...Repeated for Direct Integer Output 16
Breaker Failure (Read/Write Grouped Setting) (2, 3, 4, or 6 Modules)
B30, C60, C70,
D60, F60, G60,
L30, L60, L90,
M60, T60
8600 Breaker Failure 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" 8601 Breaker Failure 1 Mode 0 to 1 --- 1 F157 0 (3-Pole)
" 8602 Breaker Failure 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
" 8603 Breaker Failure 1 Amp Supervision 0 to 1 --- 1 F126 1 (Yes)
" 8604 Breaker Failure 1 Use Seal-In 0 to 1 --- 1 F126 1 (Yes)
" 8605 Breaker Failure 1 Three Pole Initiate 0 to 4294967295 --- 1 F300 0
" 8607 Breaker Failure 1 Block 0 to 4294967295 --- 1 F300 0
" 8609 Breaker Failure 1 Phase Amp Supv Pickup 0.02 to 30 pu 0.001 F001 1050
" 860A Breaker Failure 1 Neutral Amp Supv Pickup 0.02 to 30 pu 0.001 F001 1050
" 860B Breaker Failure 1 Use Timer 1 0 to 1 --- 1 F126 1 (Yes)
" 860C Breaker Failure 1 Timer 1 Pickup 0 to 65.535 s 0.001 F001 0
" 860D Breaker Failure 1 Use Timer 2 0 to 1 --- 1 F126 1 (Yes)
" 860E Breaker Failure 1 Timer 2 Pickup 0 to 65.535 s 0.001 F001 0
" 860F Breaker Failure 1 Use Timer 3 0 to 1 --- 1 F126 1 (Yes)
" 8610 Breaker Failure 1 Timer 3 Pickup 0 to 65.535 s 0.001 F001 0
" 8611 Breaker Failure 1 Breaker Status 1 Phase A/
3P
0 to 4294967295 --- 1 F300 0
" 8613 Breaker Failure 1 Breaker Status 2 Phase A/
3P
0 to 4294967295 --- 1 F300 0
" 8615 Breaker Failure 1 Breaker Test On 0 to 4294967295 --- 1 F300 0
" 8617 Breaker Failure 1 Phase Amp Hiset Pickup 0.02 to 30 pu 0.001 F001 1050
" 8618 Breaker Failure 1 Neutral Amp Hiset Pickup 0.02 to 30 pu 0.001 F001 1050
" 8619 Breaker Failure 1 Phase Amp Loset Pickup 0.02 to 30 pu 0.001 F001 1050
" 861A Breaker Failure 1 Neutral Amp Loset Pickup 0.02 to 30 pu 0.001 F001 1050
" 861B Breaker Failure 1 Loset Time 0 to 65.535 s 0.001 F001 0
" 861C Breaker Failure 1 Trip Dropout Delay 0 to 65.535 s 0.001 F001 0
" 861D Breaker Failure 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
" 861E Breaker Failure 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" 861F Breaker Failure 1 Phase A Initiate 0 to 4294967295 --- 1 F300 0
" 8621 Breaker Failure 1 Phase B Initiate 0 to 4294967295 --- 1 F300 0
" 8623 Breaker Failure 1 Phase C Initiate 0 to 4294967295 --- 1 F300 0
" 8625 Breaker Failure 1 Breaker Status 1 Phase B 0 to 4294967295 --- 1 F300 0
" 8627 Breaker Failure 1 Breaker Status 1 Phase C 0 to 4294967295 --- 1 F300 0
" 8629 Breaker Failure 1 Breaker Status 2 Phase B 0 to 4294967295 --- 1 F300 0
" 862B Breaker Failure 1 Breaker Status 2 Phase C 0 to 4294967295 --- 1 F300 0