2-148 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" A0AE ...Repeated for Source 6
VT Fuse Failure Actuals (Read Only) (2, 4, or 6 Modules)
C60, C70, D30,
D60, F35, F60,
G30, G60, L30,
L60, L90, M60,
N60, T60
A0B2 VTFF x V0 3rd harmonic 0 to 999999.999 V 0.001 F060 0
" A0B4 ...Repeated for Source 2
C60, C70, D60,
F35, F60, G30,
G60, L90, M60,
N60, T60
A0B6 ...Repeated for Source 3
" A0B8 ...Repeated for Source 4
C70, F35, N60,
T60
A0BA ...Repeated for Source 5
" A0BC ...Repeated for Source 6
Summator Settings (Read/Write Setting) (6 Modules)
N60 A0C0 Summator 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" A0C1 Summator 1 Input Mode 0 to 1 --- 1 F515 0 (SIGNED)
" A0C2 Summator 1 Hold 0 to 4294967295 --- 1 F300 0
" A0C4 Summator 1 Pickup –2000000 to
2000000
--- 0.001 F004 1000000
" A0C6 Summator 1 Hysteresis 0.1 to 50 % 0.1 F001 30
" A0C7 Summator 1 Input (6 items) 0 to 65535 --- 1 F600 0
" A0CD Summator 1 Scale Factor (6 items) –2000 to 2000 --- 0.000
001
F004 1000000
" A0D9 Summator 1 Position Selector (6 items) 0 to 4294967295 --- 1 F300 0
" A0E5 Summator 1 Units --- --- --- F207 (none)
" A0E7 Summator 1 Events 0 to 1 --- 1 F102 0 (Disabled)
" A0E8 Summator 1 Per-Unit Base 1 to 2000000 --- 1 F004 1
" A0EA ...Repeated for Summator 2
" A114 ...Repeated for Summator 3
" A13E ...Repeated for Summator 4
" A168 ...Repeated for Summator 5
" A192 ...Repeated for Summator 6
Current Unbalance Actual Values (Read Only)
M60 A200 Current Amp Unbalance 0 to 100 % 0.1 F001 0
Selector Switch Actual Values (Read Only)
All except B90 A210 Selector Switch 1 Position 1 to 7 --- 1 F001 0
" A211 Selector Switch 2 Position 1 to 7 --- 1 F001 1
Selector Switch Settings (Read/Write) (2 Modules)
All except B90 A280 Selector 1 Function 0 to 1 --- 1 F102 0 (Disabled)
" A281 Selector 1 Range 1 to 7 --- 1 F001 7
" A282 Selector 1 Timeout 3 to 60 s 0.1 F001 50
" A283 Selector 1 Step Up 0 to 4294967295 --- 1 F300 0
" A285 Selector 1 Step Mode 0 to 1 --- 1 F083 0 (Time-out)
" A286 Selector 1 Acknowledge 0 to 4294967295 --- 1 F300 0
" A288 Selector 1 Bit0 0 to 4294967295 --- 1 F300 0
" A28A Selector 1 Bit1 0 to 4294967295 --- 1 F300 0
" A28C Selector 1 Bit2 0 to 4294967295 --- 1 F300 0
Products Address Register name Range Units Step Format Default