Pilot Blocking 1 (1P) (Read/Write Setting)
D60, L90 A864 Blocking 1 Scheme 1P Function 0 to 1 --- 1 F102 0 (Disabled)
" A865 Blocking 1 Scheme 1P Block 0 to 4294967295 --- 1 F300 0
" A867 Block 1 1P Rx Coord Pickup Delay 0 to 65.535 s 0.001 F001 10
" A868 Block 1 1P Transient Block Pickup Delay 0 to 65.535 s 0.001 F001 30
" A869 Block 1 1P Transient Block Reset Delay 0 to 65.535 s 0.001 F001 90
" A86A Blocking 1 Scheme 1P Seal in Delay 0 to 65.535 s 0.001 F001 0
" A86B Blocking 1 Scheme 1P Dir Fwd 1 0 to 4294967295 --- 1 F300 0
" A86D Blocking 1 Scheme 1P Dir Fwd 2 0 to 4294967295 --- 1 F300 0
" A86F Blocking 1 Scheme 1P Dir Fwd 3 0 to 4294967295 --- 1 F300 0
" A871 Blocking 1 Scheme 1P Dir Rev 1 0 to 4294967295 --- 1 F300 0
" A873 Blocking 1 Scheme 1P Dir Rev 2 0 to 4294967295 --- 1 F300 0
" A875 Blocking 1 Scheme 1P Dir Rev 3 0 to 4294967295 --- 1 F300 0
" A877 Blocking 1 Scheme 1P Force Tx Stop 1 0 to 4294967295 --- 1 F300 0
" A879 Blocking 1 Scheme 1P Force Tx Stop 2 0 to 4294967295 --- 1 F300 0
" A87B Blocking 1 Scheme 1P Comm Bits 0 to 2 --- 1 F198 0 (1)
" A87C Blocking 1 Scheme 1P Rx1 0 to 4294967295 --- 1 F300 0
" A87E Blocking 1 Scheme 1P Rx2 0 to 4294967295 --- 1 F300 0
" A880 Blocking 1 Scheme 1P Rx3 0 to 4294967295 --- 1 F300 0
" A882 Blocking 1 Scheme 1P Rx4 0 to 4294967295 --- 1 F300 0
" A884 Blocking 1 1P Target 0 to 2 --- 1 F109 0 (Self-reset)
" A885 Blocking 1 1P Event 0 to 1 --- 1 F102 0 (Disabled)
Pilot POTT3 (Read/Write Setting)
F60 A886 POTT3 Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
" A887 POTT3 Scheme Block 0 to 4294967295 --- 1 F300 0
" A889 POTT3 Dir Fwd1 0 to 4294967295 --- 1 F300 0
" A88B POTT3 Dir Fwd2 0 to 4294967295 --- 1 F300 0
" A88D POTT3 Dir Fwd3 0 to 4294967295 --- 1 F300 0
" A88F POTT3 Rx 0 to 4294967295 --- 1 F300 0
" A891 POTT3 Rx Pickup Delay 0 to 65.535 s 0.001 F001 0
" A892 POTT3 Transient Block Pickup Delay 0 to 65.535 s 0.001 F001 20
" A893 POTT3 Transient Block Reset Delay 0 to 65.535 s 0.001 F001 90
" A894 POTT3 Seal In Delay 0 to 65.535 s 0.001 F001 400
" A895 POTT3 Line End Open 0 to 4294967295 --- 1 F300 0
" A897 POTT3 Line End Open Pickup Delay 0 to 65.535 s 0.001 F001 50
" A898 POTT3 Permissive Echo 0 to 1 --- 1 F102 0 (Disabled)
" A899 POTT3 Echo Duration 0 to 65.535 s 0.001 F001 100
" A89A POTT3 Echo Lockout 0 to 65.535 s 0.001 F001 250
" A89B POTT3 Target 0 to 2 --- 1 F109 0 (Self-reset)
" A89C POTT3 Events 0 to 1 --- 1 F102 0 (Disabled)
Pilot DCB3 (Read/Write Setting)
F60 A89D DCB3 Scheme Function 0 to 1 --- 1 F102 0 (Disabled)
" A89E DCB3 Scheme Block 0 to 4294967295 --- 1 F300 0
" A8A0 DCB3 Rx Coord Pickup Delay 0 to 65.535 s 0.001 F001 10
" A8A1 DCB3 Trans Block Pickup Delay 0 to 65.535 s 0.001 F001 30
" A8A2 DCB3 Trans Block Reset Delay 0 to 65.535 s 0.001 F001 90
" A8A3 DCB3 Scheme Seal In Delay 0 to 65.535 s 0.001 F001 10