EasyManua.ls Logo

GE b30 - Page 190

GE b30
526 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-170 UR FAMILY – COMMUNICATIONS GUIDE
MEMORY MAP CHAPTER 2: MODBUS COMMUNICATION
2
" C938 ...Repeated for Direct Input 43
" C93C ...Repeated for Direct Input 44
" C940 ...Repeated for Direct Input 45
" C944 ...Repeated for Direct Input 46
" C948 ...Repeated for Direct Input 47
" C94C ...Repeated for Direct Input 48
" C950 ...Repeated for Direct Input 49
" C954 ...Repeated for Direct Input 50
" C958 ...Repeated for Direct Input 51
" C95C ...Repeated for Direct Input 52
" C960 ...Repeated for Direct Input 53
" C964 ...Repeated for Direct Input 54
" C968 ...Repeated for Direct Input 55
" C96C ...Repeated for Direct Input 56
" C970 ...Repeated for Direct Input 57
" C974 ...Repeated for Direct Input 58
" C978 ...Repeated for Direct Input 59
" C97C ...Repeated for Direct Input 60
" C980 ...Repeated for Direct Input 61
" C984 ...Repeated for Direct Input 62
" C988 ...Repeated for Direct Input 63
" C98C ...Repeated for Direct Input 64
Direct Input/Output Alarms (Read/Write Setting)
All except L30,
L90
CAD0 Direct Input/Output Channel 1 CRC Alarm
Function
0 to 1 --- 1 F102 0 (Disabled)
" CAD1 Direct Input/Output Channel 1 CRC Alarm
Message Count
100 to 10000 --- 1 F001 600
" CAD2 Direct Input/Output Channel 1 CRC Alarm
Threshold
1 to 1000 --- 1 F001 10
" CAD3 Direct Input/Output Channel 1 CRC Alarm
Events
0 to 1 --- 1 F102 0 (Disabled)
" CAD4 Reserved (4 items) 1 to 1000 --- 1 F001 10
" CAD8 Direct Input/Output Channel 2 CRC Alarm
Function
0 to 1 --- 1 F102 0 (Disabled)
" CAD9 Direct Input/Output Channel 2 CRC Alarm
Message Count
100 to 10000 --- 1 F001 600
" CADA Direct Input/Output Channel 2 CRC Alarm
Threshold
1 to 1000 --- 1 F001 10
" CADB Direct Input/Output Channel 2 CRC Alarm
Events
0 to 1 --- 1 F102 0 (Disabled)
" CADC Reserved (4 items) 1 to 1000 --- 1 F001 10
" CAE0 Direct Input/Output Channel 1 Unreturned
Messages Alarm Function
0 to 1 --- 1 F102 0 (Disabled)
" CAE1 Direct Input/Output Channel 1 Unreturned
Messages Alarm Msg Count
100 to 10000 --- 1 F001 600
" CAE2 Direct Input/Output Channel 1 Unreturned
Messages Alarm Threshold
1 to 1000 --- 1 F001 10
" CAE3 Direct Input/Output Channel 1 Unreturned
Messages Alarm Events
0 to 1 --- 1 F102 0 (Disabled)
" CAE4 Reserved (4 items) 1 to 1000 --- 1 F001 10
Products Address Register name Range Units Step Format Default

Table of Contents

Other manuals for GE b30

Related product manuals