CHAPTER 2: MODBUS COMMUNICATION MEMORY MAP
UR FAMILY – COMMUNICATIONS GUIDE 2-201
2
F204
TEXT80: 80-CHARACTER ASCII TEXT
F205
TEXT12: 12-CHARACTER ASCII TEXT
F206
TEXT6: 6-CHARACTER ASCII TEXT
Unsigned 48-bit integer (three registers) numerical data. For every
16-bit register (two characters), the most-significant byte repre-
sents the first character, and the least-significant byte represents
the second character.
F207
TEXT4: 4-CHARACTER ASCII TEXT
F208
TEXT2: 2-CHARACTER ASCII TEXT
F209
TEXT65: 65-CHARACTER ASCII TEXT
F210
ENUMERATION: DIRECTION ENUMERATION
0 = IN, 1 = OUT
F211
ENUMERATION: SOURCE SELECTION
0 = None, 1 = SRC 1, 2 = SRC 2, 3 = SRC 3, 4 = SRC 4,
5 = SRC 5, 6 = SRC 6
F214
TEXT64: 64-CHARACTER ASCII TEXT
F220
ENUMERATION: PUSHBUTTON MESSAGE PRIORITY
F223
ENUMERATION: DIAGNOSTIC TEST
0 = NO TEST, 1 = RUN TEST, 2 = END TEST
F224
ENUMERATION: RATE TREND FOR FREQ RATE OF CHANGE
0 = Increasing, 1 = Decreasing, 2 = Bidirectional
F225
ENUMERATION: SPLIT PHASE PROTECTION MODE
0 = Over, 1 = Over-Under
F230
ENUMERATION: DIRECTIONAL POLARIZING
0 = Voltage, 1 = Current, 2 = Dual, 3 = Dual-V, 4 = Dual-I
F231
ENUMERATION: POLARIZING VOLTAGE
0 = Calculated V0, 1 = Measured VX
F232
ENUMERATION: CONFIGURABLE GOOSE Tx DATASET ITEMS
Value Priority
0 Disabled
1Normal
2 High Priority
Value IEC 61850 GOOSE Tx dataset
item
0None
1GGIO1.ST.Ind1.q
2 GGIO1.ST.Ind1.stVal
3GGIO1.ST.Ind2.q
4 GGIO1.ST.Ind2.stVal
↓↓
255 GGIO1.ST.Ind128.q
256 GGIO1.ST.Ind128.stVal
257 MMXU1.MX.TotW.mag.f
258 MMXU1.MX.TotVAr.mag.f
259 MMXU1.MX.TotVA.mag.f
260 MMXU1.MX.TotPF.mag.f
261 MMXU1.MX.Hz.mag.f
262 MMXU1.MX.PPV.phsAB.cVal.mag.f
263 MMXU1.MX.PPV.phsAB.cVal.ang.f
264 MMXU1.MX.PPV.phsBC.cVal.mag.f
265 MMXU1.MX.PPV.phsBC.cVal.ang.f
266 MMXU1.MX.PPV.phsCA.cVal.mag.f
267 MMXU1.MX.PPV.phsCA.cVal.ang.f
268 MMXU1.MX.PhV.phsA.cVal.mag.f
269 MMXU1.MX.PhV.phsA.cVal.ang.f
270 MMXU1.MX.PhV.phsB.cVal.mag.f
271 MMXU1.MX.PhV.phsB.cVal.ang.f
272 MMXU1.MX.PhV.phsC.cVal.mag.f
273 MMXU1.MX.PhV.phsC.cVal.ang.f
274 MMXU1.MX.A.phsA.cVal.mag.f