3-32 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.1.3 Physical device information (LPHD1)
LPHD1 is instantiated in all UR family devices.
Table 3-12: Physical device data objects
operTimeout INT32U CF 0 R
GrRef ORG Reference to root logical device R
setSrcRef ObjectReference SP For communications, mapped to
Master ldName if not empty,
otherwise to the concatenation
of the IED name and “Master.
For SCL, mapped to the
concatenation of the IED name
and “Master.
reference to the data attribute to input R
MltLev SPG Instantiated only in the Master logical
device
R
setVal BOOLEAN SP R
<TTΣDataS
et##>
DATA-SET R
DSMemberRef[η] ObjectReference DataSet Member η R/C
LNName: LPHD1LDevice inst: MasterUR element:
data obj. data attribute Type FC UR Name Description R/W/C
PhyNam DPL This physical device’s name plate R
vendor VISIBLE DC “GE Multilin R
swRev VISIBLE DC Firmware revision, e.g. “7.30” R
serNum VISIBLE DC The serial number of this
unit
.R
model VISIBLE DC The order code of this
unit
.R
location VISIBLE DC Location R/C
name VISIBLE DC RELAY NAME R/C
latitude FLOAT32 DC Latitude R/C
longitude FLOAT32 DC Longitude R/C
altitude FLOAT32 DC Altitude R/C
PhyHealt
h
ENS This physical device’s health R
stVal ENUMERATED ST 3 when ANY MAJOR ERROR==On; 2 R
Proxy SPS Indicates if this LN is a proxy R
stVal BOOLEAN ST R
RsStat SPC Mapped to command CLEAR ALL RELAY R/Ctrl
pulseConfig PulseConfig CF R
pulseConf ig
ENUMERATED 0 (pulse) R
pulseConfig.onD INT32 0 indicates the duration is locally R
pulseConf ig
INT32 0 R
pulseConf ig
INT32 1 R
ctlModel CtlModels CF
LPHD1.RsStat
.ctlModel 1, the code for direct control with normal
security; 2 is code for SBO with normal
security; 0 is for status only according to
IEC 61850-7-2. Enhanced security is not
supported as there is no means of
confirming successful execution of the
R/C
sboT
imeout INT32U CF 30000 R
sboClass SboClasses CF 0 (operate-once) R
LNName: LLN0 LDevice inst: Master UR element: Nameplate information for the logical nodes
data obj. data attribute Type FC UR Name Description R/W/C