3-36 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
3.5.1.6 Intermediate GOOSE subscription objects (GGIO3)
GGIO3 is instantiated in all UR family devices.
Table 3-17: Intermediate GOOSE subscription data objects
3.5.1.7 FlexAnalog operand interface (GGIO4)
GGIO4 is instantiated in all UR family devices.
Table 3-18: FlexAnalog data objects
LNName: GGIO3 LDevice inst: Master UR element: RxGOOSE Inputs
data obj. data attribute Type FC UR Name Description R/W/C
Indψψψ SPS RxGOOSE Booleanψ operand R
stVal BOOLEAN ST RxGOOSE Booleanψ On R
IndPosψψ DPS RxGOOSE DPSψ actual value R
stVal CODED ENUM ST R
OpnStψψ SPS RxGOOSE DPSψ Off operand R
stVal BOOLEAN ST FlexLogic operand RxGOOSE
DPSψ Off
R
ClsStψψ SPS RxGOOSE DPSψ On operand R
stVal BOOLEAN ST FlexLogic operand RxGOOSE
DPSψ On
R
BadStψψ SPS RxGOOSE DPSψ Bad operand R
stVal BOOLEAN ST FlexLogic operand RxGOOSE
DPSψ Bad
R
IntermStψ
ψ
SPS RxGOOSE DPSψ INTERM operand R
stVal BOOLEAN ST FlexLogic operand RxGOOSE
DPSψ Interm
R
AnInψψ MV RxGOOSE Analogψ operand R
mag AnalogueValue MX R
mag.f FLOAT32 RxGOOSE Analog In ψ R
units.SIUnit ENUMERATED RxGOOSE Analog # UNITS R
units.multiplier ENUMERATED RxGOOSE Analog # UNITS R
LNName: <configured GGIO4
prefix>GGIO4
LDevice inst: Master UR element: FlexAnalog Operand Interface functionality
data obj. data attribute Type FC UR Name Description R/W/C
AnInψψ MV OFF R
instMag AnalogueValue MX R
instMag.f FLOAT32 the operand selected by setting
ANALOG IN ψ VALUE
R
mag AnalogueValue MX R
mag.f FLOAT32 the operand selected by setting ANALOG
IN ψ VALUE, deadbanded
R
db INT32U CF ANALOG IN ψ DB R/W/C
zeroDb INT32U CF 0 R
DbMaxψψ ASG Value of max. in deadband calculations R
setMag AnalogueValue SP
R
setMag.f FLOAT32 ANALOG IN ψ MAX R/C
minVal AnalogueValue CF R
minVal.f FLOAT32 -1 000 000 000 000 R
maxVal AnalogueValue CF R
maxVal.f FLOAT32 1 000 000 000 000 R
stepSize AnalogueValue CF R
stepSize.f FLOAT32 0.001 R
DbMinψψ ASG Value of min. in deadband calculations R
setMag AnalogueValue SP R