CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-47
3
3.5.2.14 Capacitor bank phase overvoltage (CPhOv)
This element is instantiated in the following products: C70.
Table 3-33: C70 capacitor bank phase overvoltage function data objects
angRef ENUMERATED CF See UR product manual regarding
FREQUENCY AND PHASE REFERENCE
R
InRef2τ ORG BUS ZONE #τ STATUS setting. R
setSrcRef ObjectReference SP BUS ZONE #τ STATUS setting reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
BlkRefγ ORG BUS ZONE # DIFF BLK setting for setting
group γ.
R
setSrcRef ObjectReference SP BUS ZONE # DIFF BLK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: CPhOvPTOV# LDevice inst: Prot UR element: BANK OVERVOLTAGE element #
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD BANK OV # PKP operands (including
individual three phases), which indicates
element will operate when delay expires.
R
general BOOLEAN ST BANK OV # PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
phsA BOOLEAN ST BANK OV # PKP A R
dirPhsA ENUMERATED ST 0, the code for unknown. R
phsB BOOLEAN ST BANK OV # PKP B R
dirPhsB ENUMERATED ST 0, the code for unknown. R
phsC BOOLEAN ST BANK OV # PKP C R
dirPhsC ENUMERATED ST 0, the code for unknown. R
Op ACT BANK OV # OP operands (including
individual three phases)
R
general BOOLEAN ST BANK OV # OP R
phsA BOOLEAN ST BANK OV # OP A R
phsB BOOLEAN ST BANK OV # OP B R
phsC BOOLEAN ST BANK OV # OP C R
Dpo SPS BANK OV # DPO operand R
stVal BOOLEAN ST BANK OV # DPO R
BlkRefγ ORG BANK OV # BLK setting for setting group
γ.
R
setSrcRef ObjectReference SP BANK OV # BLK for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
OpV WYE Bank Operating Voltage in per unit for Ph
A, B, and C
R
phsA CMV R
phsA.instCVal Vector MX R
phsA.instCVal.mag
.f
FLOAT32 Bank overvoltage # phase A
operate voltage
R
phsA.cVal Vector MX R
phsA.cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
phsA.units Unit CF R
phsA.units.SIUnit ENUMERATED 1, the code for dimensionless (per unit) R
phsA.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsA.db INT32U CF CPhOvPTOV#.OpV.phsAdb R/W/C
phsA.zeroDb INT32U CF (VOLTAGE CUT-OFF LEVEL) / 275 *
100 000
R
phsB CMV R
LNName: BusDifPDIF# LDevice inst: Prot UR element: Bus Differential element # (ANSI 87B)
data obj. data attribute Type FC UR Name Description R/W/C