CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-77
3
3.5.2.46 Neutral time overcurrent (NeuToc)
This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,
T60.
Table 3-77: Neutral time overcurrent data objects
3.5.2.47 Neutral voltage unbalance (NuVUn)
This element is instantiated in the following products: C70.
Table 3-78: Neutral voltage unbalance data objects
BlkRefγ ORG NEUTRAL OV# BLK setting for setting
group γ.
R
setSrcRef ObjectReference SP NEUTRAL OV# BLK for group γ. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: NeuTocPTOC# LDevice inst: Prot UR element: Neutral Time Overcurrent element #
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD NEUTRAL TOC# PKP operand, which
indicates that Op operates when delay
expires
R
general BOOLEAN ST NEUTRAL TOC# PKP R
dirGeneral ENUMERATED ST 0, the code for unknown R
Op ACT NEUTRAL TOC# OP operand R
general BOOLEAN ST NEUTRAL TOC# OP R
Dpo SPS NEUTRAL TOC# DPO operand R
stVal BOOLEAN ST NEUTRAL TOC# DPO R
BlkRefγ1 ORG NEUTRAL TOC# BLOCK setting for setting
group γ
R
setSrcRef ObjectReference SP NEUTRAL TOC# BLOCK Reference to the data attribute to input R/C
setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/C
LNName: NuVUnPTOV# LDevice inst: Prot UR element: Neutral Voltage Unbalance element #
data obj. data attribute Type FC UR Name Description R/W/C
Mod INC This logical node’s mode R/Ctrl
stVal ENUMERATED ST 1 (on) R
ctlModel CtlModels CF 0 (status only) R
Health INS This logical node’s health R
stVal ENUMERATED ST LPHD1.PhyHealth.stVal R
Str ACD NTRL VOLT # PKP operands R
general BOOLEAN ST NTRL VOLT # PKP R
dirGeneral ENUMERATED ST 0 R
Op ACT NTRL VOLT # OP operand R
general BOOLEAN ST NTRL VOLT # OP R
Dpo SPS NTRL VOLT# DPO operand, which is the
inverse of NTRL VOLT # PKP
R
stVal BOOLEAN ST NTRL VOLT # DPO R
NeutVx CMV Neutral point voltage in p.u. R
instCVal Vector MX R
instCVal.mag.f FLOAT32 NEUTRAL-POINT Vx magnitude R
instCVal.ang.f FLOAT32 NEUTRAL-POI UR range -180...+180 converted to 0...360R
cVal Vector MX R
cVal.mag.f FLOAT32 instCVal.mag.f deadbanded R
cVal.ang.f FLOAT32 instCVal.ang.f deadbanded R
units Unit CF R
LNName: NeuOvPTOV# LDevice inst: Prot UR element: Neutral Overvoltage element # functions
data obj. data attribute Type FC UR Name Description R/W/C