CHAPTER 3: IEC 61850 COMMUNICATION MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
UR FAMILY – COMMUNICATIONS GUIDE 3-105
3
Table 3-122: Subharmonic stator ground stage data objects
3.5.2.73 Third harmonic neutral undervoltage (Ha3NUv)
This element is instantiated in the following products: G30, G60.
Table 3-123: Third harmonic neutral undervoltage data objects
3.5.2.74 Transformer instantaneous differential (PiDif)
This element is instantiated in the following products: T35, T60.
Table 3-124: Transformer instantaneous differential data objects
db INT32U CF SubHaPHIZ1.SHAmpAng.db R/W/C
zeroDb INT32U CF 0 R
BlkRefγ ORG SH STATOR GND BLK setting for setting
group γ.
R
setSrcRef ObjectReference SP SH STATOR GND BLK for group γ.reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: SubHa$PHIZ1 LDevice inst: Prot UR element: Sub-harmonic stator ground stage $ functions
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD SH STAT GND STG$ PKP operand R
general BOOLEAN ST SH STAT GND STG$ PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element may be connected/
configured to look forward or backward
R
Op ACT SH STAT GND STG$ OP operand R
general BOOLEAN ST SH STAT GND STG$ OP R
Dpo SPS SH STAT GND STG$ DPO operand R
stVal BOOLEAN ST SH STAT GND STG$ DPO R
LNName: Ha3NUvPTUV1 LDevice inst: Prot UR element: Third Harmonic Neutral Under Voltage element
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD 3RD HARM NTRL UV PKP operands R
general BOOLEAN ST 3RD HARM NTRL UV PKP R
dirGeneral ENUMERATED ST 0, the code for unknown. It is unknown as
the element is non-directional
R
Op ACT 3RD HARM NTRL UV OP operand R
general BOOLEAN ST 3RD HARM NTRL UV OP R
Dpo SPS 3RD HARM NTRL UV DPO operand, which
is the inverse of 3RD HARM NTRL UV PKP
R
stVal BOOLEAN ST 3RD HARM NTRL UV DPO R
BlkRefγ ORG 3RD HARM NTRL UV BLK setting for
setting group γ
R
setSrcRef ObjectReference SP 3RD HARM NTRL UV BLK. reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: PiDifPDIF1 LDevice inst: Prot UR element: Transformer Instantaneous Differential # function
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT XFMR INST DIFF OP , XFMR INST DIFF OP
A, XFMR INST DIFF OP B & XFMR INST DIFF
OP C operands
R
general BOOLEAN ST XFMR INST DIFF OP R
phsA BOOLEAN ST XFMR INST DIFF OP A R
phsB BOOLEAN ST XFMR INST DIFF OP B R
phsC BOOLEAN ST XFMR INST DIFF OP C R
BlkRefγ ORG INST DIFF BLOCK setting for setting group
γ.
R
LNName: SubHaPHIZ1 LDevice inst: Prot UR element: Sub-harmonic stator ground overcurrent functions
data obj. data attribute Type FC UR Name Description R/W/C