3-112 UR FAMILY – COMMUNICATIONS GUIDE
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION
3
Table 3-132: Voltage differential stage objects
3.5.2.82 Volts per Hertz (VpHz)
This element is instantiated in the following products: G30, G60, L90, T60.
Table 3-133: Volts per Hertz data objects
phsθ.cVal Vector MX R
phsθ.cVal.mag.f FLOAT32 Bus Vφ magnitude, with
deadband
R
phsθ.units Unit CF R
phsθ.units.SIUnit ENUMERATED 1, the code for dimensionless (per unit) R
phsθ.units
.multiplier
ENUMERATED 0, the code for a multiplier of 1 R
phsθ.db INT32U CF VDifPDIF#.BusVPh.phsθ.db R/W/C
phsθ.zeroDb INT32U CF 0 R
LNName: VDif$PDIF# LDevice inst: Prot UR element: Voltage Differential element # stage $
data obj. data attribute Type FC UR Name Description R/W/C
Str ACD VOLT DIF # STG$ PKP operands (including
individual three phases)
R
general BOOLEAN ST Logical OR of data attributes
phsA, phsB and phsC
R
dirGeneral ENUMERATED ST 0, the code for unknown R
phsA BOOLEAN ST VOLT DIF # STG$A PKP R
dirPhsA ENUMERATED ST 0, the code for unknown R
phsB BOOLEAN ST VOLT DIF # STG$B PKP R
dirPhsB ENUMERATED ST 0, the code for unknown R
phsC BOOLEAN ST VOLT DIF # STG$C PKP R
dirPhsC ENUMERATED ST 0, the code for unknown R
Op ACT VOLT DIF # STG$ OP operands R
general BOOLEAN ST Logical OR of data attributes
phsA, phsB, phsC
R
phsA BOOLEAN ST VOLT DIF # STG$A OP R
phsB BOOLEAN ST VOLT DIF # STG$B OP R
phsC BOOLEAN ST VOLT DIF # STG$C OP R
BlkRefγ ORG VOLT DIF # BLK STG$ setting for setting
group γ.
R
setSrcRef ObjectReference SP VOLT DIF # BLK STG$ for group
γ.
reference to the data attribute to input R/C
setSrcCB ObjectReference SP source GoCB of input if via GOOSE R/C
LNName: VpHzPVPH# LDevice inst: Prot UR element: Volts per Hertz element #
data obj. data attribute Type FC UR Name Description R/W/C
Op ACT VOLTS PER HERTZ # OP operand R
general BOOLEAN ST VOLTS PER HERTZ # OP R
Dpo SPS VOLTS PER HERTZ # DPO operand R
stVal BOOLEAN ST VOLTS PER HERTZ # DPO R
Str ACD VOLTS PER HERTZ # PKP operand R
general BOOLEAN ST VOLTS PER HERTZ # PKP operand R
dirGeneral ENUMERATED ST 0 R
BlkRefγ ORG VOLTS /HZ # BLOCK setting for setting
group γ
R
setSrcRef ObjectReference SP VOLTS/HZ # BLOCK for group γ Reference to the data attribute to input R/C
setSrcCB ObjectReference SP Source GoCB of input if via GOOSE R/C
LNName: VDifPDIF# LDevice inst: Prot UR element: Voltage Differential element # core functions
data obj. data attribute Type FC UR Name Description R/W/C